Skip to main content
Schneider Electric LP2K06013BD3 — Contactors

Schneider Electric LP2K06013BD3 TeSys K Reversing Contactor,

MPNLP2K06013BD3
Obsolete

Schneider Electric TeSys K reversing contactor, LP2K06013BD3, 3P, AC-3 ≤440 V 6 A, 1 NC, 24 V DC coil, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LP2K06013BD3 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LP2K06013BD3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3
LP2K06013BD3 — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K06013BD3 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K06013BD3 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The LP2K06013BD3 is a TeSys K reversing contactor from Schneider Electric — a preassembled 3-pole unit with an integral reversing power busbar, rated for AC-3 motor duty at 6 A up to 440 V and AC-4 duty for inching/jogging applications. The 24 V DC coil and one normally-closed auxiliary contact are built in; the contactor carries an IP20 finger-safe enclosure per VDE 0106, so it mounts in a standard control panel without additional shrouding on the terminals.

This part is listed as Obsolete by the manufacturer. The TeSys K series has been superseded by the TeSys Deca range in most applications, but pin-to-pin compatibility depends on the mounting footprint and coil voltage; verify the panel layout before substituting.

Rated operational voltage on the power circuit is 690 V AC 50/60 Hz, though the AC-3 motor rating is specified at ≤440 V. The contactor handles vibration up to 4 Gn closed (5–300 Hz per IEC 60068-2-6) and shock at 15 Gn closed on the Z axis — figures that matter for mobile or skid-mounted equipment. Flame retardance meets UL 94 V1 and NF F 16-101/102, which is typical for rail and transit panel specs.

Frequently asked questions

What are the key ratings for the LP2K06013BD3?

It is a 3-pole reversing contactor rated AC-3 at 6 A up to 440 V, with a 24 V DC coil and one NC auxiliary contact. The power circuit is rated for 690 V AC 50/60 Hz, and the enclosure is IP20.

What compliance documentation is available for this part?

The contactor carries a V1 flame retardance rating per UL 94 and meets NF F 16-101/102 for rail applications. IP20 protection is per VDE 0106. No RoHS or REACH statements appear in the available records.

MPN
LP2K06013BD3