Skip to main content
Schneider Electric LRD15106 — Overload Relays

Schneider TeSys LRD15106 Thermal Overload Relay, 4-6 A, Clas

MPNLRD15106
Obsolete

Schneider Electric TeSys Deca LRD15106 differential thermal overload relay, 4-6 A, Class 20, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LRD15106 — Mechanical
ParameterValue
Width45 mm
Depth92 mm

Product details

The Schneider Electric TeSys Deca LRD15106 is a differential thermal overload relay for motor protection, with a thermal protection adjustment range of 4 to 6 A and a Class 20 tripping characteristic conforming to IEC 60947-4-1. It provides phase-failure sensitivity — tripping at 130 % of Ir on two phases with the third at zero — and a tripping threshold of 1.14 ± 0.06 Ir per IEC 60947-4-1.

Mounts under a contactor, on a plate, or on a DIN rail with specific accessories. Power circuit connections use lugs-ring terminals (torque 2.3 N·m); control circuit uses screw-clamp terminals accepting 1 to 2.5 mm² flexible or solid wire (torque 1.7 N·m).

Frequently asked questions

What is the thermal protection adjustment range of the LRD15106?

The adjustment range is 4 to 6 A, with a Class 20 tripping characteristic per IEC 60947-4-1.

What standards does the LRD15106 comply with?

It complies with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, and CSA C22.2 No 60947-4-1 and 60947-5-1.

MPN
LRD15106