Its thermal protection adjustment range covers 48…65 A, meaning it directly matches motors drawing full-load current in that band — no external CTs or scaling needed. Rated thermal overload class 10A per IEC 60947-4-1, so it trips within 10 seconds at 7.2× Ir — fast enough to protect standard induction motors during a locked-rotor event without nuisance tripping on normal starts. Phase-failure sensitivity is built in: the relay trips at 130 % of Ir on two phases when the third drops to zero, which is the standard IEC requirement for preventing single-phasing damage.
Mounts directly under a TeSys D or TeSys F contactor, or on a DIN rail with specific accessories. The 70 mm width and 115 mm depth keep the footprint compact for dense panel layouts — no extra side clearance needed for the reset push-button. Power circuit connections use lugs-ring terminals (M10, torque 11.3 N·m); control circuit wiring uses screw-clamp terminals accepting 1…2.5 mm² flexible or solid. The 17.5 mm connection pitch aligns with standard terminal-block spacing.
Certified to IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, and GB/T 14048.4 / 14048.5 — so it is accepted in panels destined for North America, Europe, and China without additional component-level testing.