Skip to main content
Schneider Electric LT4760BS — Auxiliary Contacts

Schneider Electric LT4760BS

MPNLT4760BS
Active

Electronic over current relays, TeSys LT47, manual, 5 to 60A, 24VAC/DC

$61.29 – $120.18Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

LT4760BS — Identification
ParameterValue
Product typeElectronic overcurrent relay
Product range / familyTeSys
Product name / familyTeSys LT
LT4760BS — Ratings
ParameterValue
Conventional free-air thermal current (Ith)3 A for signalling circuit
Network frequency50...60 Hz
LT4760BS — Contacts & Poles
ParameterValue
Auxiliary contact composition1 NO + 1 NC
LT4760BS — Performance
ParameterValue
Rated insulation voltage (Ui)Power circuit: 600 V AC conforming to CSA Power circuit: 600 V AC conforming to UL Power circuit: 690 V AC conforming to IEC 60947-4-1
Rated impulse withstand voltage (Uimp)6 kV
LT4760BS — Mechanical
ParameterValue
Terminal connections / wire rangeSignalling circuit: screw clamp terminals 1 1...2.5 mm² - cable stiffness: flexible with cable end Signalling circuit: screw clamp terminals 1 1...2.5 mm² - cable stiffness: flexible without cable end Signalling circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Signalling circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible without cable end
Terminal tightening torqueSignalling circuit: 1.7 N.m M3.5
IP degree of protectionIP20 conforming to IEC 60529 IP20 conforming to VDE 0106
Width71 mm
Height70.3 mm
Depth77.2 mm
LT4760BS — Environmental
ParameterValue
Operating ambient temperature-25...60 °C without derating conforming to IEC 60947-4-1
Storage ambient temperature-30...80 °C
Operating altitude2000 m
Protective treatmentTH conforming to IEC 60068
LT4760BS — Approvals
ParameterValue
StandardsIEC 60947 IEC 60255-6
LT4760BS — Electrical
ParameterValue
Tripping threshold5...50 A
[Us] rated supply voltage24 V AC 24 V DC
LT4760BS — Specifications
ParameterValue
Thermal protection adjustment range5...60 A
Time range0.5..30 s - control type D-time 0.3...10 s - control type O-time
Control typepush-button: reset electrical: reset
LT4760BS — I/O
ParameterValue
Relay applicationOverload Imax > Isetting Sensitivity to phase failure Locked rotor, mechanical jamming I > 3 x Isetting
MPN
LT4760BS