Schneider Electric LUB32TQ
MPNLUB32TQ
Obsolete
Power base, TeSys U, 3P, 32A/690V, TQ 10
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Non reversing power base |
| Product range | TeSys |
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | 690 V AC for power circuit |
| Network frequency | 40...60 Hz |
| Pole configuration | 3P |
| Parameter | Value |
|---|---|
| Terminal connection capacity | Control circuit: screw clamp terminals 1 cable(s) 0.34...1.5 mm² flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 0.75...1.5 mm² flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 0.75...1.5 mm² rigid Control circuit: screw clamp terminals 2 cable(s) 0.34...1.5 mm² flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 0.75...1.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 0.75...1.5 mm² rigid Power circuit: screw clamp terminals 1 cable(s) 1...10 mm² rigid Power circuit: screw clamp terminals 1 cable(s) 1...6 mm² flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 2.5...10 mm² flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 1...6 mm² flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1...6 mm² rigid Power circuit: screw clamp terminals 2 cable(s) 1.5...6 mm² flexible without cable end |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 154 mm |
| Depth | 126 mm |
| Parameter | Value |
|---|---|
| IP protection rating | IP20 conforming to IEC 60947-1 (front panel and wired terminals) IP20 conforming to IEC 60947-1 (other faces) IP40 conforming to IEC 60947-1 (front panel outside connection zone) |
| Operating ambient temperature | -25...60 °C with LUCM -25...70 °C with LUCA, LUCB, LUCC, LUCD |
| Storage ambient temperature | -40...85 °C |
| Operating altitude | 2000 m |
| Fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12 650 °C conforming to IEC 60695-2-12 |
| Parameter | Value |
|---|---|
| Conformance standards | EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier |
MPN
LUB32TQ