Schneider Electric LV429830
MPNLV429830
Obsolete
Circuit breaker, ComPact NSX100N, 50kA/415VAC, MicroLogic 2.2M trip unit 100A, 3 poles 3d
$293.93Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Range of product | ComPact NSX100...250 |
| Product or component type | Circuit breaker |
| Long-time protection delay adjustment type tr | Fixed |
| Short-time protection delay adjustment type tsd | Fixed |
| Short-time protection pick-up adjustment type isd | Adjustable 9 settings |
| Instantaneous protection pick-up adjustment type ii | Fixed |
| Long-time pick-up adjustment type ir (thermal protection) | Adjustable 9 settings |
| Voltage | 800 V AC 50/60 Hz |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
All specifications
| Parameter | Value |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| Line rated current | 100 A 149 °F (65 °C) |
| [Ics] rated service short-circuit breaking capacity | 10 kA 660/690 V AC 50/60 Hz IEC 60947-2 35 kA 525 V AC 50/60 Hz IEC 60947-2 36 kA 500 V AC 50/60 Hz IEC 60947-2 50 kA 380/415 V AC 50/60 Hz IEC 60947-2 50 kA 440 V AC 50/60 Hz IEC 60947-2 90 kA 220/240 V AC 50/60 Hz IEC 60947-2 |
| [Icu] rated ultimate short-circuit breaking capacity | 85 kA 240 V AC 50/60 Hz UL 508 10 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2 35 kA Icu 525 V AC 50/60 Hz IEC 60947-2 20 kA 600 V AC 50/60 Hz UL 508 50 kA 480 V AC 50/60 Hz UL 508 36 kA Icu 500 V AC 50/60 Hz IEC 60947-2 50 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 90 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 |
| Network frequency | 50/60 Hz |
| Poles | 3P |
| Protected poles description | 3t |
| Utilisation category | Category A |
| IK degree of protection | IK07 conforming to IEC 62262 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Mounting support | Backplate |
| Circuit breaker mounting mode | Fixed |
| Connection pitch | 1.4 in (35 mm) |
| Upside connection | Front |
| Downside connection | Front |
| Pollution degree | 3 IEC 60664-1 |
| Relative humidity | 0...95 % |
| Operating altitude | 0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating |
| Electrical shock protection class | Class II |
| Depth | 3.4 in (86 mm) |
| Width | 4.1 in (105 mm) |
| Height | 6.3 in (161 mm) |
| Electrical durability | 10000 cycles 690 V In 20000 cycles 690 V In/2 30000 cycles 440 V In 50000 cycles 440 V In/2 |
| Mechanical durability | 50000 cycles |
| Standards | EN/IEC 60947 |
| Range | ComPact |
| Thermal memory | 20 minutes before and after tripping |
| Trip unit name | MicroLogic 2.2 M |
| Local signalling | Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point |
| Trip unit rating | 100 A 149 °F (65 °C) |
| Device short name | NSX100N |
| Safety category | N 50 kA 415 V AC |
| Device application | Motor |
| Motor tripping class | 20 10 5 |
| Overvoltage category | Class II |
| Trip unit technology | Electronic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes EN/IEC 60947-2 |
| Complementary motor protection | Phase unbalance |
| Trip unit protection functions | LSoI |
| Zone selective interlocking ZSI | Without |
| Ambient air temperature for storage | -58...185 °F (-50...85 °C) |
| Ambient air temperature for operation | -13...158 °F (-25...70 °C) |
| Number of slots for electrical auxiliaries | 5 |
| [Tr] Long-Time protection delay adjustment range | 10 s 7.2 x Ir 10 120 s 1.5 x Ir 5 20 s 7.2 x Ir 20 240 s 1.5 x Ir 10 26 s 6 x Ir 20 480 s 1.5 x Ir 20 5 s 7.2 x Ir 5 13.5 s 6 x Ir 10 6.5 s 6 x Ir 5 |
| [Ir] long-time protection pick-up adjustment range | 50...100 A |
| [Isd] short-time protection pick-up adjustment range | 5...13 x Ir |
| [Ii] instantaneous protection pick-up adjustment range | 1500 A |
MPN