Skip to main content
Schneider Electric LV838921

Schneider LV838921 MasterPact MTZ2 1600A, 200kA Icu, Obsolet

MPN LV838921
Active

Schneider Electric MasterPact MTZ2, LV838921, 3-pole drawout circuit breaker, 1600 A rated, LF breaking capacity, 600 VAC UL 489.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV838921 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Terminal pitch4.5 in (115 mm)
Depth16.8 in (426.8 mm)
Width17.5 in (444.3 mm)
Height17.3 in (438.8 mm)
ApplicationProtection
Safety category200 kA Icu 240 V AC 50/60 Hz UL 489 150 kA Icu 480 V AC 50/60 Hz UL 489 100 kA Icu 600 V AC 50/60 Hz UL 489

Product details

The LV838921 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 1600 A at 104 °F (40 °C) with LF breaking capacity — meaning 200 kA Icu at 240 V AC, 150 kA Icu at 480 V AC, and 100 kA Icu at 600 V AC per UL 489. That's a serious main or feeder breaker for a 600 V class switchboard, sized to handle a 1600 A bus without cascading upstream. The drawout chassis lets you rack the breaker in and out for maintenance or swap without disturbing the bus connections — standard for large-frame power breakers in industrial and commercial distribution.

The integral instant protection trips between 49.5 and 55.5 kA — that's the magnetic-only short-circuit pickup range, set at the factory for this LF code. Maximum breaking time is 9 ms; closing response is 70 ms. Physical footprint: 17.5 in wide, 17.3 in tall, 16.8 in deep — that's the drawout cassette envelope. Mounting is on base plate rails with a 4.5 in (115 mm) connection pitch. Network frequency is 50/60 Hz.

MPN
LV838921