Skip to main content
Schneider Electric LV839004 — Air Circuit Breakers

LV839004 Masterpact MTZ3 50 HA Switch Disconnector, 5000A

MPNLV839004
Active

Schneider Electric Masterpact MTZ3 50 HA, LV839004, non-automatic switch disconnector, 5000 A rated, 4-pole drawout, ANSI C37.50 rated.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV839004 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution
LV839004 — Electrical ratings
ParameterValue
Rated operational current (Ie)5000 A 104 °F (40 °C)
Poles4P
Network typeAC
Network frequency50/60 Hz
LV839004 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85.0 kA 0.5 s ANSI C37.50
Breaking capacity65.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50
LV839004 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width40.5 in (1028.7 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)

Product details

The LV839004 is a Masterpact MTZ3 50 HA non-automatic switch disconnector from Schneider Electric, rated for 5000 A at 104 °F (40 °C) in a 4-pole drawout chassis mount. This is a distribution-class device built to ANSI C37.50 standards, carrying a 65 kA Icu breaking capacity at 254 V, 508 V, and 635 V AC 50/60 Hz when used with an external relay. The short-time withstand current [Icw] is 85 kA for 0.5 s per ANSI C37.50, which gives the coordination engineer headroom for selective tripping downstream.

Sizing and deployment context

At 5000 A continuous, this switch sits at the main or feeder level in a low-voltage distribution switchboard. The drawout mounting means it pulls out for inspection or replacement without de-energizing the bus — a feature the maintenance planner will appreciate for line-up downtime. The 4-pole configuration covers three-phase plus neutral, common for North American 277/480 V wye or 347/600 V wye services.

The 65 kA Icu rating holds across the full voltage range (254 V through 635 V AC) with an external relay per ANSI C37.50. That flat curve is unusual — most breakers derate as voltage rises. For the site electrical engineer, this means the same SCCR applies whether the service is 480 V or 600 V, simplifying the coordination study. The 85 kA Icw for 0.5 s lets downstream breakers clear a fault before this device trips, keeping selective coordination intact.

Physical integration

The chassis-mounted drawout cassette measures 40.5 in (1028.7 mm) wide, 18.8 in (478.1 mm) high, and 16.8 in (426.8 mm) deep. Connection pitch is 9.06 in (230 mm). The panel OEM needs to verify the cutout and gland plate dimensions against the switchboard layout — these are large-frame dimensions for a 5000 A device. Push-button control is integral to the front escutcheon.

Frequently asked questions

What is the breaking capacity of LV839004?

The LV839004 has a 65 kA Icu breaking capacity at 254 V, 508 V, and 635 V AC 50/60 Hz when used with an external relay per ANSI C37.50. The short-time withstand current [Icw] is 85 kA for 0.5 s.

Where can I buy LV839004 and how is it quoted?

The LV839004 is sourced and quoted to order against an RFQ through independent industrial distribution channels. Availability and current pricing are confirmed at the time of quote — no stock figures or lead-time numbers are published here.

What are the physical dimensions of LV839004?

The LV839004 drawout cassette measures 40.5 in (1028.7 mm) wide, 18.8 in (478.1 mm) high, and 16.8 in (426.8 mm) deep, with a connection pitch of 9.06 in (230 mm).

MPN