Skip to main content
Schneider Electric LV839008 — Air Circuit Breakers

Schneider Electric LV839008 Masterpact MTZ3 60 HA, 6000A, 4P

MPNLV839008
Active

Schneider Electric Masterpact MTZ3 60 HA, LV839008, Non-Automatic switch disconnector, 6000A, ANSI, 4P, drawout.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV839008 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution
LV839008 — Electrical ratings
ParameterValue
Rated operational current (Ie)6000 A 104 °F (40 °C)
Poles4P
Network typeAC
Network frequency50/60 Hz
LV839008 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85.0 kA 0.5 s ANSI C37.50
Breaking capacity65.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50
LV839008 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width40.5 in (1028.7 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)

Product details

The LV839008 is a Schneider Electric Masterpact MTZ3 60 HA non-automatic switch disconnector rated at 6000 A continuous at 40 °C ambient. It's a 4-pole drawout unit built for ANSI distribution applications — think main or tie switch in large low-voltage switchgear where you need to manually isolate a bus section or a transformer feeder. Breaking capacity is 65 kA Icu at 254 V, 508 V, and 635 V AC 50/60 Hz when used with an external relay per ANSI C37.50. The short-time withstand current (Icw) is 85 kA for 0.5 s per ANSI C37.50 — a key number for selective coordination studies: downstream breakers can clear a fault while this switch holds closed through the delay. Control is push-button operated, and the drawout chassis mounting lets you rack the unit out for maintenance without unbolting bus connections — standard for switchgear where uptime and isolation safety matter.

Frequently asked questions

What is the breaking capacity of LV839008?

The LV839008 has a breaking capacity of 65 kA Icu at 254 V, 508 V, and 635 V AC 50/60 Hz when used with an external relay per ANSI C37.50.

Where can I buy LV839008 and how is it quoted?

The LV839008 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and target delivery.

MPN
LV839008