Skip to main content
Schneider Electric LV839027 — Air Circuit Breakers

Schneider Electric MasterPact MTZ3 LV839027, 4000 A, 3P, Dra

MPNLV839027
Active

Schneider Electric MasterPact MTZ3, LV839027, 3-pole drawout circuit breaker, 4000 A rated at 40 °C, H3 breaking capacity (100 kA Icu at 508 V AC), without Micrologic trip unit.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839027 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ3
ApplicationProtection

Electrical ratings

LV839027 — Electrical ratings
ParameterValue
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839027 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85 kA 0.5 s ANSI C37.50
Breaking capacity codeH3

Performance

LV839027 — Performance
ParameterValue
Breaking time, max.25...30 ms
Closing response time, max.70 ms
Mechanical durability (cycles)10000 cycles ANSI C37.50
Electrical durability (cycles)1000 cycles ANSI C37.50

Mechanical & connection

LV839027 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBase plate Rails
Width31.07 in (789.1 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)

Product details

The LV839027 is a Schneider Electric MasterPact MTZ3 drawout circuit breaker, 3-pole, rated 4000 A at 40 °C, with H3 breaking capacity delivering 100 kA Icu at 508 V AC per ANSI C37.50. It ships without a Micrologic trip unit — the buyer sources the protection relay separately to match the coordination study. The drawout cradle allows the breaker to be racked out for maintenance without disturbing the bus connections, standard for large ANSI switchgear.

The H3 frame gives 100 kA Icu at 254 V AC, 100 kA Icu at 508 V AC, and 85 kA Icu at 635 V AC. The rated short-time withstand current (Icw) is 85 kA for 0.5 s, which supports delayed tripping for zone-selective interlocking — critical for coordinating downstream feeders without sacrificing arc-flash energy. The integral instantaneous protection range is 171–209 kA, and the rated breaking and making capacity is 170 kA. Maximum breaking time is 25–30 ms; maximum closing response time is 70 ms.

Physical integration

The drawout chassis mounts on base plate rails. Overall dimensions: width 31.07 in (789.1 mm), height 18.8 in (478.1 mm), depth 16.8 in (426.8 mm) (–). Connection pitch is 9.06 in (230 mm). The breaker is designed for ANSI switchgear lineups — verify the cradle cutout and bus spacing against the existing gear before ordering.

Frequently asked questions

How do I get current pricing and availability for LV839027?

Pricing and availability are confirmed at quote time against an RFQ. Submit a request with the desired quantity and any required accessories (trip unit, shunt trip, etc.) for a current quote.

What is the closest alternative to LV839027 in the MasterPact MTZ3 family?

The LV839027 is the 4000 A, 3-pole, H3 breaking capacity variant without a Micrologic trip unit. A pin-compatible alternative would be the same frame with a different rating (e.g., 3200 A or 5000 A) or a different breaking capacity code (H1, H2). The drawout cradle and physical footprint are shared across the MTZ3 range, but the trip unit selection and protection settings must match the application.

What compliance documentation does Schneider Electric provide for LV839027?

The MasterPact MTZ3 series carries UL, CSA, and ANSI certifications per the ANSI C37.50 standard cited in the ratings. The specific documentation package (RoHS, REACH, UL file number) is provided with the shipment or available on request.

MPN