Schneider Electric LV839029 — Air Circuit Breakers

Schneider LV839029 MasterPact MTZ3 4000A 4P Drawout, 100 kA

MPNLV839029
Active

Schneider Electric MasterPact MTZ3, LV839029, 4000 A rated, 4-pole drawout, H3 breaking capacity 100 kA Icu at 508 V AC ANSI C37.50, without Micrologic trip unit.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839029 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ3
ApplicationProtection

Electrical ratings

LV839029 — Electrical ratings
ParameterValue
Poles4P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839029 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85 kA 0.5 s ANSI C37.50
Breaking capacity codeH3

Performance

LV839029 — Performance
ParameterValue
Breaking time, max.25...30 ms
Closing response time, max.70 ms
Mechanical durability (cycles)12500 cycles ANSI C37.50
Electrical durability (cycles)2800 cycles ANSI C37.50

Mechanical & connection

LV839029 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBase plate Rails
Width40.5 in (1028.7 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Neutral pole positionLeft
Connection pitch9.06 in (230 mm)

Product details

The LV839029 is a MasterPact MTZ3 frame drawout circuit breaker rated 4000 A continuous at 104 °F (40 °C) — that is the full-frame current, not a derated number, so it carries the main bus without a bump. The H3 breaking capacity delivers 100 kA Icu at 508 V AC per ANSI C37.50, meaning it safely interrupts a fault up to that level and recloses without service. For a 635 V AC system the Icu drops to 85 kA, still enough for most industrial secondary-distribution switchgear. The short-time withstand (Icw) is 85 kA for 0.5 s, which is the figure you use for selective coordination with downstream feeders — if your upstream breaker clears in under half a cycle, this frame holds closed and lets the downstream device isolate the fault. Integral instantaneous protection trips between 171 kA and 209 kA — that is the magnetic-only floor, not the adjustable pickup. The 25–30 ms maximum break time and 70 ms maximum closing response time are the mechanism's native speed; they govern arc-flash incident energy calculations for the IEEE 1584 study. Mechanical durability is 12,500 cycles, electrical durability 2,800 cycles per ANSI C37.50 — both are the mechanism's life before major overhaul, not the trip-unit life.

Drawout mounting and panel fit

This is a drawout chassis — the breaker cassette slides into a fixed cradle, so you can rack it out for maintenance without unbolting bus bars. The mounting support is base plate rails; the connection pitch is 9.06 in (230 mm) between phase centers, which is the standard MasterPact MTZ footprint. Panel cutout dimensions: width 40.5 in (1028.7 mm), height 18.8 in (478.1 mm), depth 16.8 in (426.8 mm). No Micrologic trip unit is included — you order the trip unit separately to match your protection curve (LSIG, LSI, or G).

Frequently asked questions

What breaking capacity does LV839029 provide at 508 V AC?

100 kA Icu at 508 V AC per ANSI C37.50, with the H3 breaking capacity code. At 635 V AC the Icu is 85 kA, and the short-time withstand (Icw) is 85 kA for 0.5 s.

What are the panel cutout dimensions for LV839029?

Width 40.5 in (1028.7 mm), height 18.8 in (478.1 mm), depth 16.8 in (426.8 mm). The connection pitch between phase centers is 9.06 in (230 mm).

Where can I buy LV839029 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the current lead time.