Skip to main content
Schneider Electric LV839056 — Air Circuit Breakers

Schneider Electric LV839056 Masterpact MTZ3 40 HF, 4000A, 3P

MPNLV839056
Active

Schneider Electric Masterpact MTZ3 40 HF, LV839056, switch disconnector, 4000 A, 3P, fixed, ANSI.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839056 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839056 — Electrical ratings
ParameterValue
Rated operational current (Ie)4000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839056 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85.0 kA 1.5 s ANSI C37.50
Breaking capacity100.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 100.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 85.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839056 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Width30.2 in (767 mm)
Height13.9 in (352.2 mm)
Depth11.7 in (297.1 mm)
Connection pitch9.06 in (230 mm)

Other specifications

LV839056 — Other specifications
ParameterValue
Device short nameMTZ3 40 HF

Product details

The Schneider Electric LV839056 is a Masterpact MTZ3 40 HF switch disconnector rated for 4000 A at 104 °F (40 °C), 3-pole, fixed-mount, designed for distribution applications per ANSI C37.50. The part carries a breaking capacity of 100 kA Icu at 254 V AC 50/60 Hz with an external relay, and 85 kA Icu at 635 V AC — meaning it can safely interrupt fault currents up to those levels without upstream cascading, critical for selectivity studies in large switchboards.

The 4000 A rated operational current (Ie) at 40 °C sets the continuous load capacity — sized for high-current feeders or main incomers in industrial or utility distribution. The short-time withstand current (Icw) of 85 kA for 1.5 s per ANSI C37.50 defines the thermal and dynamic stress the switch can handle during a delayed fault clearing; this is the figure coordination engineers use to verify the switch survives downstream breaker clearing time. Dimensions are 30.2 in (767 mm) wide, 13.9 in (352.2 mm) tall, and 11.7 in (297.1 mm) deep — these govern the panel cutout and mounting footprint for fixed-mount installations.

Frequently asked questions

What is the breaking capacity of LV839056?

The LV839056 has a breaking capacity of 100 kA Icu at 254 V AC 50/60 Hz with an external relay, 100 kA Icu at 508 V AC, and 85 kA Icu at 635 V AC, all per ANSI C37.50.

Where can I buy LV839056?

The LV839056 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN