Skip to main content
Schneider Electric LV839058 — Air Circuit Breakers

LV839058 Masterpact MTZ3 40 HF Switch Disconnector, 4000 A

MPNLV839058
Active

Schneider Electric Masterpact MTZ3 40 HF, LV839058, automatic switch disconnector, 4000 A, 4P, fixed mounting, 100 kA Icu at 254 V AC.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839058 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839058 — Electrical ratings
ParameterValue
Rated operational current (Ie)4000 A 104 °F (40 °C)
Poles4P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839058 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85.0 kA 1.5 s ANSI C37.50
Breaking capacity100.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 100.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 85.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839058 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Width39.2 in (996.3 mm)
Height13.9 in (352.2 mm)
Depth11.7 in (297.1 mm)
Connection pitch9.06 in (230 mm)

Other specifications

LV839058 — Other specifications
ParameterValue
Device short nameMTZ3 40 HF

Product details

The LV839058 is a Masterpact MTZ3 40 HF automatic switch disconnector rated 4000 A at 104 °F (40 °C) — that is the continuous current it carries without derating, so for a 4000 A bus or feeder this is the frame size. The 100 kA Icu at 254 V AC (with external relay, per ANSI C37.50) tells you it can interrupt a fault up to that level without failing; the 85 kA Icw for 1.5 s is the short-time withstand, which governs selectivity coordination with downstream breakers. Four poles, fixed mount, push-button control. This is a distribution-class device, not a motor-protection breaker — it goes on the main or tie bus.

Fixed mounting means the breaker bolts directly to a mounting plate or bus structure — no draw-out cradle. The 39.2 in (996.3 mm) width and 13.9 in (352.2 mm) height define the cutout and clearance envelope; depth is 11.7 in (297.1 mm) including the push-button operator. Connection pitch is 9.06 in (230 mm) between phase centers, which matches standard bus-bar spacing for 4000 A switchgear. Plan for front-access cable or bus connections; the fixed chassis does not slide out for maintenance.

Frequently asked questions

What is the breaking capacity of LV839058?

100 kA Icu at 254 V AC and 508 V AC, and 85 kA Icu at 635 V AC, all with external relay per ANSI C37.50. The short-time withstand is 85 kA for 1.5 s.

Where can I buy LV839058?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — no stock count or price published here.

MPN