Skip to main content
Schneider Electric LV839060 — Air Circuit Breakers

LV839060 Masterpact MTZ3 50 HF, 5000A, 3P, Fixed Switch Disc

MPNLV839060
Active

Schneider Electric Masterpact MTZ3 50 HF, automatic switch disconnector, 5000 A, ANSI, 3P, fixed mounting, push-button control, 100 kA Icu at 254 V AC.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839060 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839060 — Electrical ratings
ParameterValue
Rated operational current (Ie)5000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839060 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85.0 kA 1.5 s ANSI C37.50
Breaking capacity100.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 100.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 85.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839060 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Width30.2 in (767 mm)
Height13.9 in (352.2 mm)
Depth11.7 in (297.1 mm)
Connection pitch9.06 in (230 mm)

Other specifications

LV839060 — Other specifications
ParameterValue
Device short nameMTZ3 50 HF

Product details

The Schneider Electric LV839060 is a Masterpact MTZ3 50 HF automatic switch disconnector, rated 5000 A at 104 °F (40 °C) in a 3-pole fixed configuration. It's built for distribution duty on AC networks at 50/60 Hz, with push-button control and a fixed mounting mode that bolts directly into the switchgear lineup — no DIN-rail play here, this thing lands on a panel floor or chassis. The headline number that matters for selectivity coordination is the breaking capacity: 100 kA Icu at 254 V AC and 508 V AC, and 85 kA Icu at 635 V AC, all with an external relay per ANSI C37.50. Short-time withstand current is rated at 85 kA for 1.5 seconds per ANSI C37.50, which tells you it can ride through a delayed trip coordination scheme without damage. That's the spec you check when you're cascading breakers downstream and need the main to hold for a couple of cycles while the branch clears.

At 30.2 in (767 mm) wide, 13.9 in (352.2 mm) tall, and 11.7 in (297.1 mm) deep, this is a large-frame switch that needs a dedicated cutout or mounting plate. The connection pitch of 9.06 in (230 mm) sets the bus-bar or cable landing spacing — verify your existing bus centers before committing the BOM line.

Frequently asked questions

Where can I buy LV839060 and how do I get a price?

The LV839060 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not before.

What is LV839060's breaking capacity at 254 V AC?

The LV839060 carries a breaking capacity of 100 kA Icu at 254 V AC 50/60 Hz with an external relay per ANSI C37.50.

MPN
LV839060