Skip to main content
Schneider Electric LV839067 — Air Circuit Breakers

Schneider Electric LV839067 Masterpact MTZ3 60 HF, 6000A, 4P

MPNLV839067
Active

Schneider Electric Masterpact MTZ3 60 HF, LV839067, switch disconnector, 6000 A, 4-pole, drawout, ANSI.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839067 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution
LV839067 — Electrical ratings
ParameterValue
Rated operational current (Ie)6000 A 104 °F (40 °C)
Poles4P
Network typeAC
Network frequency50/60 Hz
LV839067 — Breaking & withstand capacity
ParameterValue
Breaking capacity100.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 100.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 85.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50
LV839067 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width40.5 in (1028.7 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)
LV839067 — Other specifications
ParameterValue
Device short nameMTZ3 60 HF

Product details

The LV839067 is a Masterpact MTZ3 60 HF automatic switch disconnector rated 6000 A at 104 °F (40 °C), 4-pole, drawout chassis mount, for AC distribution networks at 50/60 Hz. Breaking capacity reaches 100 kA Icu at 254 V AC and 508 V AC, and 85 kA Icu at 635 V AC — all with an external relay per ANSI C37.50. That means it clears a fault up to 100 kA without the arc flashing over, which is the selectivity headroom a site electrical engineer needs for coordination studies on a large switchboard. The drawout cradle lets you rack the breaker out for maintenance or swap without disturbing the bus connections — a field-service tech can isolate and replace this in minutes, not hours.

Physical footprint and integration

Width is 40.5 in (1028.7 mm), depth 16.8 in (426.8 mm), height 18.8 in (478.1 mm). Connection pitch is 9.06 in (230 mm). That is a large-frame breaker — plan the enclosure gland plate and bus-bar takeoff accordingly. Mounts on a chassis with drawout mechanism; the panel OEM wireman needs to account for the racking clearance in front of the cubicle.

Frequently asked questions

What is LV839067's rated breaking capacity?

100 kA Icu at 254 V AC and 508 V AC, and 85 kA Icu at 635 V AC — all with an external relay per ANSI C37.50.

What are the physical dimensions of LV839067?

Width 40.5 in (1028.7 mm), depth 16.8 in (426.8 mm), height 18.8 in (478.1 mm). Connection pitch is 9.06 in (230 mm).

MPN
LV839067