Skip to main content
Schneider Electric LV839092 — Air Circuit Breakers

Schneider LV839092 MTZ3 50 HC Switch Disconnector, 5000 A

MPNLV839092
Active

Schneider Electric Masterpact MTZ3 50 HC, LV839092, switch disconnector, 5000 A, ANSI, 3P, fixed mount, push-button control.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839092 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839092 — Electrical ratings
ParameterValue
Rated operational current (Ie)5000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839092 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)100.0 kA 1.5 s ANSI C37.50
Breaking capacity200.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 200.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 130.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839092 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Width30.2 in (767 mm)
Height13.9 in (352.2 mm)
Depth11.7 in (297.7 mm)
Connection pitch9.06 in (230 mm)

Other specifications

LV839092 — Other specifications
ParameterValue
Device short nameMTZ3 50 HC

Product details

The LV839092 is a Schneider Electric Masterpact MTZ3 50 HC switch disconnector rated for 5000 A at 104 °F (40 °C) in a 3-pole fixed-mount configuration. It's built for distribution duty with a push-button control interface and AC network type.

Breaking capacity and withstand

Breaking capacity steps: 200 kA Icu at 254 V AC, 200 kA Icu at 508 V AC, and 130 kA Icu at 635 V AC — all with an external relay per ANSI C37.50. The short-time withstand current (Icw) is 100 kA for 1.5 s per the same standard. For a 5000 A frame, these numbers put it in the high-capability tier of the Masterpact family.

Physical envelope: 30.2 in (767 mm) wide, 13.9 in (352.2 mm) tall, 11.7 in (297.7 mm) deep. Connection pitch is 9.06 in (230 mm) — that's the center-to-center spacing for the bus bars or cable lugs on each pole. Fixed-mount chassis means it bolts directly to a mounting plate or sub-base; no draw-out cradle. Panel builders need to account for the 30-inch width when laying out the switchboard section — that's a full cubicle width in most ANSI gear.

Frequently asked questions

What is the breaking capacity of LV839092?

The LV839092 has a breaking capacity of 200 kA Icu at 254 V AC, 200 kA Icu at 508 V AC, and 130 kA Icu at 635 V AC, all with an external relay per ANSI C37.50. The short-time withstand current is 100 kA for 1.5 s.

Where can I buy LV839092?

The LV839092 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN