Skip to main content
Schneider Electric LV839093 — Air Circuit Breakers

LV839093 Masterpact MTZ3 50 HC 5000A 3P Drawout Switch Disco

MPNLV839093
Active

Schneider Electric Masterpact MTZ3 50 HC, LV839093, switch disconnector, 5000 A, ANSI, 3P, drawout.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839093 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839093 — Electrical ratings
ParameterValue
Rated operational current (Ie)5000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839093 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)100.0 kA 1.5 s ANSI C37.50
Breaking capacity200.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 200.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 130.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839093 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width31.07 in (789.1 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)

Product details

The LV839093 is a Schneider Electric Masterpact MTZ3 50 HC switch disconnector, rated 5000 A at 104 °F (40 °C) for distribution duty. Its 200 kA Icu at 508 V AC 50/60 Hz (with external relay, per ANSI C37.50) means it can safely interrupt fault currents up to that level without upstream damage — the number that governs the SCCR for the entire downstream panel. The 100 kA Icw for 1.5 s (ANSI C37.50) tells you it withstands a delayed trip coordination window, which is the selectivity parameter a site electrical engineer needs to verify against the upstream breaker curve.

Drawout chassis mounting — panel integration

Drawout mounting on a chassis support means this 3-pole unit slides in and out of a fixed cradle — no need to disconnect main power cables for maintenance or swap-out. The 16.8 in depth, 31.07 in width, and 18.8 in height (–) define the cutout and clearance envelope in the switchgear lineup; the 9.06 in (230 mm) connection pitch sets the bus-bar drilling pattern. For a panel OEM or site planner, those dimensions are the first fit check before the crane lift.

Frequently asked questions

What is LV839093's breaking capacity?

200 kA Icu at 508 V AC 50/60 Hz with external relay per ANSI C37.50, and 130 kA Icu at 635 V AC under the same conditions. The 100 kA Icw for 1.5 s supports selective coordination.

Where can I buy LV839093 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price is published here.