Skip to main content
Schneider Electric LV839099 — Air Circuit Breakers

Schneider LV839099 MasterPact MTZ2 1600A 3P Drawout, 200kA I

MPNLV839099
Active

Schneider Electric MasterPact MTZ2, LV839099, 3-pole drawout circuit breaker, 1600 A rated at 40 °C, L1F breaking capacity, 200 kA Icu at 254 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839099 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
ApplicationProtection
LV839099 — Electrical ratings
ParameterValue
Poles3P
Network typeAC
Network frequency50/60 Hz
LV839099 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)22 kA 0.5 s ANSI C37.50
Breaking capacity codeL1F
LV839099 — Performance
ParameterValue
Breaking time, max.9 ms
Closing response time, max.70 ms
Mechanical durability (cycles)12500 cycles ANSI C37.50
Electrical durability (cycles)2800 cycles ANSI C37.50
LV839099 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBase plate Rails
Width17.5 in (444.3 mm)
Height17.3 in (438.8 mm)
Depth16.8 in (426.8 mm)
Connection pitch4.5 in (115 mm)

Product details

The LV839099 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 1600 A continuous at 40 °C ambient. That 1600 A frame covers large secondary transformers, main feeders, or generator incomers in ANSI-distribution gear. The L1F breaking capacity code delivers 200 kA Icu at 254 V AC and 130 kA Icu at 635 V AC per ANSI C37.50 — meaning it can safely interrupt fault currents up to that level without upstream cascading. Short-time withstand (Icw) is 22 kA for 0.5 s, which governs coordination with downstream breakers during a delayed trip. Mechanical endurance is 12,500 cycles, electrical endurance 2,800 cycles under ANSI C37.50. The integral instantaneous protection is set at 49.5 to 55.5 kA — a fixed magnetic range for bolted-fault clearing. Maximum break time is 9 ms, closing response 70 ms. Drawout mounting (4.5-inch connection pitch) means the breaker slides onto base-plate rails for racking in and out without disturbing power wiring — standard for switchgear where isolation for maintenance is required.

Frequently asked questions

Where can I buy LV839099 and how do I get a price?

The LV839099 is sourced to order through independent distribution against an RFQ. Submit a request for quote; availability and current pricing are confirmed at that time.

What is LV839099's breaking capacity at 254 V and 635 V?

The LV839099 carries 200 kA Icu at 254 V AC and 130 kA Icu at 635 V AC, both per ANSI C37.50. Short-time withstand is 22 kA for 0.5 s.

What are the physical dimensions of LV839099?

Depth is 16.8 in (426.8 mm), width 17.5 in (444.3 mm), height 17.3 in (438.8 mm). Connection pitch is 4.5 in (115 mm).

MPN