Skip to main content
Schneider Electric LV839108 — Air Circuit Breakers

Schneider LV839108 MasterPact MTZ1 800A 3P Fixed Circuit Bre

MPNLV839108
Active

Schneider Electric MasterPact MTZ1, LV839108, UL 489 circuit breaker, 800 A rated, 3 pole, fixed mount, H breaking capacity, 65 kA Icu 240 V AC, 50/60 Hz.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839108 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ1
ApplicationProtection

Electrical ratings

LV839108 — Electrical ratings
ParameterValue
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839108 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)35 kA 0.5 s UL 489
Breaking capacity codeH

Performance

LV839108 — Performance
ParameterValue
Breaking time, max.25...30 ms
Closing response time, max.50 ms
Mechanical durability (cycles)10000 cycles ANSI C37.50
Electrical durability (cycles)1000 cycles ANSI C37.50

Mechanical & connection

LV839108 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate Rails
Width10.9 in (276.2 mm)
Height11.8 in (300.5 mm)
Depth8.2 in (209 mm)
Connection pitch2.8 in (70 mm)

Product details

What this MasterPact MTZ1 delivers

The LV839108 is a fixed-mount MasterPact MTZ1 circuit breaker from Schneider Electric, rated 800 A at 40 °C, 3-pole, with H breaking capacity code. It carries UL 489 listing and delivers 65 kA Icu at 240 V AC, 50 kA Icu at 480 V AC, and 50 kA Icu at 600 V AC — the interrupting rating you need to match the available fault current at your service entrance or distribution panel. The 35 kA Icw (0.5 s per UL 489) gives you short-time withstand for selective coordination downstream. Mechanical durability is rated at 10,000 cycles (ANSI C37.50), electrical durability at 1,000 cycles — figures that tell you this breaker is built for main or feeder duty where you cycle it infrequently but need it to clear faults reliably. The integral instant protection range of 81–99 kA means the magnetic trip acts fast on high faults, while the 25–30 ms maximum breaking time keeps arc energy contained.

Fixed mounting on base plate rails, with a connection pitch of 70 mm. Dimensions: width 276.2 mm, height 300.5 mm, depth 209 mm. That depth (8.2 in) matters when you're laying out the gland plate or door clearance — it's a standard drawout-equivalent footprint for the MTZ1 frame.

Frequently asked questions

What are the key interrupting ratings for LV839108?

It delivers 65 kA Icu at 240 V AC, 50 kA Icu at 480 V AC, and 50 kA Icu at 600 V AC, all per UL 489. Short-time withstand (Icw) is 35 kA for 0.5 s.

How do I get current pricing and availability for LV839108?

Submit an RFQ — we source through independent distribution and confirm price and lead time at quote. No stock figures or prices are listed here.

What is LV839108's listed depth?

The depth is 209 mm (8.2 in).

What compliance documentation does this breaker carry?

The LV839108 is UL 489 listed for the USA and Canada. It is designed for 50/60 Hz AC networks. RoHS and REACH compliance is standard for Schneider's MasterPact range, but specific declarations should be requested with the RFQ.

MPN