Skip to main content
Schneider Electric LV839162 — Air Circuit Breakers

LV839162 Masterpact MTZ2 30 HB, 3000A, 3P, Drawout

MPNLV839162
Active

Schneider Electric Masterpact MTZ2 30 HB, automatic switch disconnector, 3000 A, UL, 3P, drawout, ArcBlok.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839162 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839162 — Electrical ratings
ParameterValue
Rated operational current (Ie)3000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839162 — Breaking & withstand capacity
ParameterValue
Breaking capacity200.0 kA Icu 240 V AC 50/60 Hz UL 489 150.0 kA Icu 480 V AC 50/60 Hz UL 489 100.0 kA Icu 600 V AC 50/60 Hz UL 489

Mechanical & connection

LV839162 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width17.5 in (444.3 mm)
Height17.3 in (438.8 mm)
Depth16.8 in (426.8 mm)
Connection pitch4.5 in (115 mm)

Product details

The LV839162 is a Schneider Electric Masterpact MTZ2 30 HB automatic switch disconnector rated for 3000 A at 40 °C, 3-pole, drawout chassis mount. This is the high-current distribution breaker for a 480 V or 600 V main — the 200 kA Icu at 240 V AC and 100 kA Icu at 600 V AC per UL 489 tell you it handles fault currents up to those levels without upstream coordination failure. The drawout cradle means the breaker slides out for maintenance or swap without disturbing the bus connections, which is the standard for switchboard mains and large feeder positions.

The 200 kA Icu at 240 V AC, 150 kA at 480 V AC, and 100 kA at 600 V AC (all 50/60 Hz, UL 489) define the maximum fault current this breaker can safely interrupt. For a 3000 A main on a 480 V service with a transformer capable of 150 kA symmetrical fault current, this breaker holds — no need for a current-limiting fuse upstream. The integral instant protection at 150 kA sets the magnetic trip threshold; verify coordination with downstream feeders per the selectivity tables in the MTZ2 documentation.

Drawout mounting on a chassis with a connection pitch of 4.5 in (115 mm). Overall dimensions: 17.5 in wide × 17.3 in tall × 16.8 in deep (444.3 × 438.8 × 426.8 mm). The drawout cradle requires matching cutout and bus-stab alignment in the switchboard — verify the existing cradle model (MTZ2 drawout) accepts this 3P 3000 A frame before ordering.

Frequently asked questions

How do I get current pricing and availability for LV839162?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and stock levels are confirmed at quote time.

What is the closest alternative to LV839162 in the Masterpact MTZ2 family?

Within the MTZ2 30 HB frame, the primary variant difference is the rated current rating (3000 A for this code) and the integral protection settings. A lower-current MTZ2 30 HB (e.g., 2000 A) shares the same drawout cradle and physical footprint but uses a different rating plug. No pin-compatible drop-in exists — the rating plug and trip unit must match the specified continuous current.

What compliance documentation does LV839162 carry?

The UL 489 listing is the primary certification for North American distribution applications. The Masterpact MTZ2 series also carries IEC 60947-2 compliance. RoHS and REACH declarations are available from Schneider Electric per standard documentation for current-production items.

MPN