Skip to main content
Schneider Electric LV839164 — Air Circuit Breakers

Schneider Electric LV839164 MasterPact MTZ2 1200A 3P Drawout

MPNLV839164
Obsolete

Schneider Electric MasterPact MTZ2, LV839164, 1200 A, 3-pole, drawout, LF breaking capacity, 600 VAC, UL 489, with ArcBlok.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV839164 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
ApplicationProtection
LV839164 — Electrical ratings
ParameterValue
Poles3P
Network typeAC
Network frequency50/60 Hz
LV839164 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)22 kA 0.5 s UL 489
Breaking capacity codeLF
LV839164 — Performance
ParameterValue
Breaking time, max.9 ms
Closing response time, max.70 ms
Mechanical durability (cycles)10000 cycles ANSI C37.50
Electrical durability (cycles)1000 cycles ANSI C37.50
LV839164 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBase plate Rails
Width17.5 in (444.3 mm)
Height17.3 in (438.8 mm)
Depth16.8 in (426.8 mm)
Connection pitch4.5 in (115 mm)

Product details

The LV839164 is a MasterPact MTZ2 drawout circuit breaker rated 1200 A continuous at 40 °C, 3-pole, with LF breaking capacity code. It carries UL 489 listings: 200 kA Icu at 240 V AC, 150 kA Icu at 480 V AC, and 100 kA Icu at 600 V AC — these are the fault-current levels it can safely interrupt without self-destruction, so the SCCR of the downstream panel must be coordinated against these values. The ArcBlok technology (integral instant protection set 49.5...55.5 kA) limits arc energy during a short-circuit event, reducing the pressure wave inside the enclosure.

Schneider Electric has marked the LV839164 as obsolete. If you are holding a panel design that specifies the MTZ2 drawout footprint, verify whether a current-production MasterPact MTZ frame (MTZ1, MTZ2, MTZ3) with equivalent ratings can be substituted; the drawout cradle and bus connections differ across frame sizes.

Drawout mounting on base-plate rails — the breaker slides into a fixed cradle with a 4.5 in (115 mm) connection pitch. The overall envelope is 17.5 in wide × 17.3 in tall × 16.8 in deep (444.3 × 438.8 × 426.8 mm). That depth includes the ArcBlok arc-chamber housing; verify the enclosure depth allows the full drawout racking travel before the breaker is committed to the panel layout.

Performance and durability

Mechanical durability is rated at 10,000 cycles per ANSI C37.50; electrical durability at 1,000 cycles under the same standard. Maximum breaking time is 9 ms, with a maximum closing response time of 70 ms. The short-time withstand current (Icw) is 22 kA for 0.5 s per UL 489 — this governs how long the breaker can carry fault current while waiting for a downstream device to clear, critical for selective coordination studies.

Frequently asked questions

Where can I buy LV839164?

The LV839164 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What are the key UL 489 breaking capacities for LV839164?

200 kA Icu at 240 V AC, 150 kA Icu at 480 V AC, and 100 kA Icu at 600 V AC — all per UL 489. These are the maximum fault currents the breaker can interrupt at those voltages.

What is the rated continuous current of LV839164?

1200 A at 40 °C (104 °F) ambient. The breaker is also fitted with a 1200 A CT rating for its integral protection.

What compliance documentation does Schneider provide for LV839164?

The part carries UL 489 listing for the US market. RoHS, REACH, and other compliance documents are typically available from Schneider Electric's product documentation portal for the MasterPact MTZ2 series.

MPN
LV839164