Skip to main content
Schneider Electric LV839194 — Air Circuit Breakers

LV839194 MasterPact MTZ2 800A 3P Drawout, 200kA Icu

MPNLV839194
Active

Schneider Electric MasterPact MTZ2, LV839194, 3-pole drawout circuit breaker, 800A rated, breaking capacity, 635VAC, ArcBlok.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839194 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
ApplicationProtection
LV839194 — Electrical ratings
ParameterValue
Poles3P
Network typeAC
Network frequency50/60 Hz
LV839194 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)30 kA 0.5 s ANSI C37.50
Breaking capacity codeL1
LV839194 — Performance
ParameterValue
Breaking time, max.9 ms
Closing response time, max.70 ms
Mechanical durability (cycles)12500 cycles ANSI C37.50
Electrical durability (cycles)2800 cycles ANSI C37.50
LV839194 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBase plate Rails
Width17.5 in (444.3 mm)
Height17.3 in (438.8 mm)
Depth16.8 in (426.8 mm)
Connection pitch4.5 in (115 mm)

Product details

The LV839194 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 800 A at 40 °C. It carries an breaking capacity code with interrupting ratings up to 200 kA Icu at 254 V AC 60 Hz per ANSI C37.50, stepping down to 100 kA Icu at 635 V AC 50 Hz. The ArcBlok technology inside this frame reduces arc energy during interruption, which helps with switchgear coordination and extends contact life. Drawout mounting means the breaker slides into a cradle — you can rack it out for maintenance or replacement without unbolting bus connections. The base plate rails and 4.5 in connection pitch match standard ANSI switchgear cubicle layouts. Mechanical durability is rated at 12,500 cycles, electrical durability at 2,800 cycles under ANSI C37.50. Maximum breaking time is 9 ms, with a closing response time of 70 ms. The integral instantaneous protection range is 72 to 88 kA.

Sourcing reality — obsolete, but available

Schneider Electric has marked the LV839194 as obsolete.

Frequently asked questions

Where can I buy LV839194 and how do I get a price?

The LV839194 is sourced through independent distribution and surplus channels. Submit an RFQ against this order code; availability and current pricing are confirmed at quote time.

What are the interrupting ratings for LV839194?

Per ANSI C37.50, the LV839194 delivers 200 kA Icu at 254 V AC 60 Hz, 150 kA Icu at 508 V AC 60 Hz, 130 kA Icu at 635 V AC 60 Hz, and corresponding ratings at 50 Hz: 200 kA at 254 V, 150 kA at 508 V, 100 kA at 635 V.

What is the rated current and pole configuration of LV839194?

It is a 3-pole breaker rated 800 A continuous at 40 °C ambient.

MPN