LV839202 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ3
ApplicationProtection
LV839202 — Electrical ratings
ParameterValue
Poles3P
Network typeAC
Network frequency50/60 Hz
LV839202 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)22 kA 0.5 s ANSI C37.50
Breaking capacity codeL1F
LV839202 — Performance
ParameterValue
Breaking time, max.9 ms
Closing response time, max.70 ms
Mechanical durability (cycles)5000 cycles ANSI C37.50
Electrical durability (cycles)1000 cycles ANSI C37.50
LV839202 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBase plate Rails
Width17.5 in (444.3 mm)
Height17.3 in (438.8 mm)
Depth16.8 in (426.8 mm)
Connection pitch4.5 in (115 mm)

Product details

The Schneider Electric LV839202 is a MasterPact MTZ3 drawout circuit breaker, 3-pole, rated 2000 A at 40 °C. It carries the L1F breaking capacity code, delivering 200 kA Icu at 254 V AC and 508 V AC, and 130 kA Icu at 635 V AC per ANSI C37.50. The integral instantaneous protection trips between 49.5 and 55.5 kA. This is a main or feeder breaker for large low-voltage switchgear — sized for a 2000 A bus, not a branch panel.

The L1F breaking capacity (200 kA Icu at 254/508 V, 130 kA at 635 V) tells you the maximum fault current the breaker can safely interrupt; verify your available fault current at the point of installation stays under these thresholds. The short-time withstand (Icw) is 22 kA for 0.5 s — this matters for selective coordination downstream, where the breaker must hold in during a fault long enough for a branch breaker to clear.

Drawout mount with a 4.5-inch (115 mm) connection pitch. The breaker slides into a cassette on base-plate rails — no bolted bus connections to torque. Panel cutout and depth (16.8 in / 426.8 mm) must accommodate the drawout mechanism and ArcBlok arc-chamber. Width is 17.5 in (444.3 mm), height 17.3 in (438.8 mm).

Frequently asked questions

Where can I buy LV839202?

The LV839202 is sourced through independent distribution on a quoted-to-order basis. Submit an RFQ for current availability and pricing — no stock figures or lead-time numbers are carried here.

What is the breaking capacity of LV839202?

The L1F breaking capacity delivers 200 kA Icu at 254 V AC and 508 V AC, and 130 kA Icu at 635 V AC, all per ANSI C37.50.

What is the rated current of LV839202?

The line rated current is 2000 A at 40 °C (104 °F).