Schneider Electric LV839229 — Air Circuit Breakers

Schneider Electric LV839229 MX Com Opening Coil, 200-250 V A

MPNLV839229
Obsolete

Schneider Electric, MasterPact MTZ, MX communicating opening voltage release, LV839229, 200-250 V AC/DC, drawout mounting, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839229 — Identification
ParameterValue
Product typeVoltage release
ApplicationControl
LV839229 — Mechanical & connection
ParameterValue
Mounting modeDrawout
LV839229 — Other specifications
ParameterValue
Response time50 ms +/- 10 % MasterPact MTZ1 50 ms +/- 10 % MasterPact MTZ2 50 ms +/- 10 % MasterPact MTZ3
Device short nameMX com
Supply holding power4.5 VA 4.5 W
Voltage release typeOpening coil
Threshold tripping voltage0.7...1.1 Un
Coil voltage200...250 V AC 50/60 Hz 200...250 V DC

Product details

The LV839229 is a Schneider Electric MX communicating opening voltage release for MasterPact MTZ drawout circuit breakers. It's the coil that trips the breaker on loss of control voltage or remote command — a control function, not a protection relay. Control circuit voltage is 200-250 V AC 50/60 Hz or 200-250 V DC, with a tripping threshold of 0.7 to 1.1 Un. Holding power sits at 4.5 VA / 4.5 W, so the control transformer or DC supply needs to sustain that continuously.

This part is marked obsolete by Schneider Electric. That means the factory line is closed — no last-time-buy window remains open. If you're maintaining an MTZ fleet, this is the kind of spare that gets harder to find each quarter; a cross-reference to a non-communicating MX coil or a third-party equivalent may be worth evaluating for new builds.

Drawout mounting means this coil plugs into the MasterPact MTZ cradle — it's not for fixed-mounted breakers. The 50 ms ±10% response time applies across MTZ1, MTZ2, and MTZ3 frames; that's the mechanical opening time once the coil sees the trip threshold. The 0.7-1.1 Un tripping window means it releases when the control voltage drops to 70% of nominal — useful for undervoltage protection schemes — and holds in up to 110% without nuisance tripping. The MX 'com' variant adds communication capability, so it can be tripped remotely via the breaker's control bus, not just by hardwired contacts.

Frequently asked questions

How do I get current pricing and availability for LV839229?

Submit an RFQ through this listing. We source obsolete Schneider parts through independent distribution and can confirm availability and current pricing at quote time.

What is LV839229's listed mounting mode?

Drawout mounting — it's designed for the MasterPact MTZ drawout cradle, not for fixed-mounted breaker installations.

What is LV839229's response time?

50 ms ±10% for MasterPact MTZ1, MTZ2, and MTZ3 frames. That's the mechanical opening time once the coil is energized to the trip threshold.