Schneider Electric LV839233 — Air Circuit Breakers

Schneider LV839233 MX Opening Voltage Release, 24 V AC/DC, M

MPNLV839233
Obsolete

Schneider Electric, MasterPact MTZ, MX opening voltage release, LV839233, 24 V AC 50/60 Hz / 24-30 V DC, drawout mounting, 50 ms response time.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839233 — Identification
ParameterValue
Product typeVoltage release
ApplicationControl
LV839233 — Mechanical & connection
ParameterValue
Mounting modeDrawout
LV839233 — Other specifications
ParameterValue
Response time50 ms +/- 10 % MasterPact MTZ1 50 ms +/- 10 % MasterPact MTZ2 50 ms +/- 10 % MasterPact MTZ3
Device short nameMX
Supply holding power4.5 VA 4.5 W
Voltage release typeOpening coil
Threshold tripping voltage0.7...1.1 Un
Coil voltage24 V AC 50/60 Hz 24...30 V DC

Product details

The Schneider LV839233 is an MX-type opening voltage release designed for MasterPact MTZ drawout circuit breakers. It mounts into the drawout chassis — not bolted to a panel — so it slides in with the breaker cradle and connects through the racking mechanism. The part is a control accessory, not a standalone device: it trips the breaker when its control voltage is applied or removed, depending on the release function (opening coil).

That dual-range AC/DC input is common on Schneider MX coils — it means the same part works in a panel with a 24 VDC control bus or a 24 VAC transformer supply. The threshold tripping voltage is 0.7 to 1.1 times the rated control voltage (Un), so the coil will reliably operate between about 17 V and 33 V for the DC variant. Holding power is 4.5 VA / 4.5 W — a standard control transformer or DC supply handles that without derating. Response time is 50 ms ±10% across all MTZ frames — MTZ1, MTZ2, and MTZ3. That means from the moment the trip signal hits the coil terminals to the breaker opening, you're looking at roughly 45-55 ms. For a line-down scenario, that's fast enough for most coordination schemes; if you need faster, you'd be looking at a different release type (e.g., a shunt trip with a different response curve).

Frequently asked questions

What is LV839233's listed mounting mode?

Drawout mounting. It installs into the MasterPact MTZ drawout chassis — the same cradle that racks the breaker in and out. No panel-mounting hardware is needed; the release slides into the designated slot in the cradle and connects through the racking mechanism.

What is the response time of LV839233?

50 ms ±10% across all MasterPact MTZ frames — MTZ1, MTZ2, and MTZ3. That means the coil opens the breaker in roughly 45-55 ms from signal application.

Where can I buy LV839233?

We source this obsolete part to order against an RFQ through independent distribution — surplus stock, decommissioned lines, and broker channels. Availability and current pricing are confirmed at quote time; submit an RFQ with your quantity and we'll respond the same business day.

MPN