Skip to main content
Schneider Electric LV839250 — Air Circuit Breakers

Schneider Electric LV839250 XF com Closing Coil, 200-250 V A

MPNLV839250
Obsolete

Schneider Electric LV839250, XF com communicating closing voltage release, 200-250 V AC/DC, for MasterPact MTZ drawout breakers.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839250 — Identification
ParameterValue
Product typeVoltage release
ApplicationControl
LV839250 — Mechanical & connection
ParameterValue
Control typeCommunicating
Mounting modeDrawout
LV839250 — Other specifications
ParameterValue
Response time55 ms +/- 10 % MasterPact MTZ1 70 ms +/- 10 % MasterPact MTZ2 80 ms +/- 10 % MasterPact MTZ3
Device short nameXF com
Signalling functionError Ready to close or open Coil powered Electrical push-button activated
Supply holding power4.5 VA 4.5 W
Voltage release typeClosing coil
Threshold tripping voltage0.85...1.1 Un
Coil voltage200...250 V AC 50/60 Hz 200...250 V DC

Product details

The LV839250 is a communicating closing voltage release (XF com) for Schneider Electric MasterPact MTZ drawout circuit breakers. It operates on a 200-250 V AC 50/60 Hz or 200-250 V DC control circuit, with a threshold tripping voltage of 0.85 to 1.1 Un. Supply holding power is 4.5 VA / 4.5 W.

This part is obsolete per the manufacturer. No direct successor is listed in the evidence.

The communicating control type means this closing coil integrates with the MasterPact MTZ's communication bus — it reports status (error, ready to close, coil powered, push-button activated) back to the controller, not just a dry contact. The drawout mounting mode confirms it's designed for the MTZ drawout cradle, not the fixed version. Response time varies by frame: 55 ms +/- 10% for MTZ1, 70 ms for MTZ2, 80 ms for MTZ3 — factor that into your trip-coordination timing budget.

Deployment Context

Installs into the MasterPact MTZ drawout chassis — the drawout mechanism allows the breaker to be racked out for maintenance without disturbing control wiring. The closing coil is wired to the control circuit (200-250 V AC/DC) and communicates via the breaker's internal bus. Verify the control voltage matches your panel supply before commissioning.

Frequently asked questions

What is the control type of LV839250?

The LV839250 has a communicating control type (XF com), meaning it reports status signals (error, ready to close, coil powered, push-button activated) over the MasterPact MTZ communication bus.

What is the mounting mode of LV839250?

The LV839250 uses a drawout mounting mode, designed for the MasterPact MTZ drawout cradle.

MPN