Skip to main content
Schneider Electric LV839255 — Air Circuit Breakers

Schneider Electric LV839255 XF closing coil, 48 V AC/DC, for

MPNLV839255
Obsolete

Schneider Electric, MasterPact MTZ series, XF closing voltage release, LV839255, 48 V AC 50/60 Hz / 48-60 V DC control circuit, drawout mounting.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839255 — Identification
ParameterValue
Product typeVoltage release
ApplicationControl
LV839255 — Mechanical & connection
ParameterValue
Mounting modeDrawout
LV839255 — Other specifications
ParameterValue
Response time55 ms +/- 10 % MasterPact MTZ1 70 ms +/- 10 % MasterPact MTZ2 80 ms +/- 10 % MasterPact MTZ3
Device short nameXF
Supply holding power4.5 VA 4.5 W
Voltage release typeClosing coil
Threshold tripping voltage0.85...1.1 Un
Coil voltage48 V AC 50/60 Hz 48...60 V DC

Product details

The Schneider Electric LV839255 is an XF closing voltage release — a solenoid-style closing coil — designed for MasterPact MTZ drawout circuit breakers. It energizes the breaker's closing mechanism when the control voltage is applied, allowing remote or automatic closing of the main contacts. Control circuit voltage is 48 V AC at 50/60 Hz or 48 to 60 V DC, with a threshold tripping voltage range of 0.85 to 1.1 times the nominal voltage (Un). Holding power draws 4.5 VA (AC) or 4.5 W (DC). Response time is frame-dependent: 55 ms ±10% on MTZ1, 70 ms ±10% on MTZ2, and 80 ms ±10% on MTZ3. The drawout mounting mode means this coil installs into the breaker's drawout cradle, not the fixed portion — relevant when specifying spare parts for a drawout chassis.

The 48 V AC / 48-60 V DC control voltage is the critical fit parameter — this coil will not operate on 24 V or 110 V control power. The 0.85 to 1.1 Un threshold means the coil picks up reliably at 40.8 V AC (0.85 × 48 V) and must not see sustained voltage above 52.8 V AC (1.1 × 48 V). On the DC side, the acceptable range is 40.8 V to 66 V DC. Holding power of 4.5 VA / 4.5 W is modest — the control transformer or DC supply only needs to support that continuous draw once the coil is sealed. The inrush is higher but brief; the response time figures (55-80 ms) include the mechanical travel of the closing mechanism.

Frequently asked questions

Where can I buy LV839255?

The LV839255 is sourced through independent distribution channels — new-old-stock or verified surplus. Availability and current pricing are confirmed at quote time against an RFQ; it is not stocked on the shelf.

What is the mounting mode for LV839255?

Drawout mounting. The coil installs into the drawout cradle of a MasterPact MTZ breaker, not the fixed chassis. This is the standard accessory interface for MTZ drawout frames.

What is the response time of LV839255?

Response time depends on the breaker frame: 55 ms ±10% on MasterPact MTZ1, 70 ms ±10% on MTZ2, and 80 ms ±10% on MTZ3. These figures include both the electrical pickup delay and the mechanical travel of the closing mechanism.

MPN
LV839255