Skip to main content
Schneider Electric LV839257 — Air Circuit Breakers

Schneider LV839257 XF Closing Coil, 200-250V AC/DC, for MTZ

MPNLV839257
Obsolete

Schneider Electric, MasterPact MTZ, XF closing voltage release, LV839257, 200-250 V AC/DC, drawout mounting, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839257 — Identification
ParameterValue
Product typeVoltage release
ApplicationControl
LV839257 — Mechanical & connection
ParameterValue
Mounting modeDrawout
LV839257 — Other specifications
ParameterValue
Response time55 ms +/- 10 % MasterPact MTZ1 70 ms +/- 10 % MasterPact MTZ2 80 ms +/- 10 % MasterPact MTZ3
Device short nameXF
Supply holding power4.5 VA 4.5 W
Voltage release typeClosing coil
Threshold tripping voltage0.85...1.1 Un
Coil voltage200...250 V AC 50/60 Hz 200...250 V DC

Product details

The LV839257 is an XF closing voltage release — a closing coil — designed for Schneider Electric MasterPact MTZ drawout circuit breakers. It operates on a 200-250 V AC 50/60 Hz or 200-250 V DC control circuit, with a threshold tripping voltage of 0.85 to 1.1 times the nominal control voltage (Un).

The drawout mounting mode means this coil is not a panel-mount standalone device — it plugs into the MasterPact MTZ breaker's drawout cassette. If your breaker is a fixed-mount MTZ, this coil will not fit without the drawout cradle. The response time varies by frame size: 55 ms ±10% for MTZ1, 70 ms ±10% for MTZ2, and 80 ms ±10% for MTZ3. That timing matters if your control scheme sequences multiple breakers and needs coordinated closing delays.

Holding power is rated at 4.5 VA (AC) or 4.5 W (DC) — a light continuous load on the control transformer, but verify the control circuit's minimum load rating if you are switching it through a PLC output card. The Device Application is listed as Control, meaning it is intended for closing the breaker under command, not for protection tripping.

Frequently asked questions

Where can I buy LV839257 and how do I get a price?

We source this obsolete part through our independent distribution network. Submit an RFQ — we confirm availability and current pricing at quote time. No stock count or price is published because the supply is variable.

What is LV839257's mounting mode?

Drawout. It is designed to plug into the MasterPact MTZ drawout cassette, not for fixed-mount breakers or standalone panel installation.

What control voltage does LV839257 accept?

200-250 V AC at 50/60 Hz, or 200-250 V DC. The tripping threshold is 0.85 to 1.1 times the nominal control voltage (Un).

MPN
LV839257