Skip to main content
Schneider Electric LV839268 — Air Circuit Breakers

Schneider Electric LV839268 MN Diagnostic Undervoltage Relea

MPNLV839268
Obsolete

Schneider Electric MasterPact MTZ, MN diagnostic undervoltage release, 200-250 V AC/DC, drawout, safety device.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV839268 — Identification
ParameterValue
Product typeVoltage release
ApplicationSafety
LV839268 — Mechanical & connection
ParameterValue
Control typeCommunicating
Mounting modeDrawout
LV839268 — Other specifications
ParameterValue
Response time40 ms +/- 5 % MasterPact MTZ1 90 ms +/- 5 % MasterPact MTZ2 90 ms +/- 5 % MasterPact MTZ3
Device short nameMN diag
Signalling functionCoil powered MN open Error
Supply holding power4.5 W 4.5 VA
Voltage release typeUndervoltage release
Threshold tripping voltage0.35...0.7 Un on opening 0.85 Un on closing
Coil voltage200...250 V AC 50/60 Hz 200...250 V DC

Product details

The Schneider Electric LV839268 is an MN diagnostic undervoltage release for MasterPact MTZ drawout circuit breakers. It monitors the control circuit voltage and trips the breaker when voltage drops below the threshold — a safety function that prevents motor or equipment restart after a power dip.

Tripping threshold is 0.35 to 0.7 Un on opening and 0.85 Un on closing. Holding power draw is 4.5 W / 4.5 VA. Response time is 40 ms ±5% on MasterPact MTZ1, and 90 ms ±5% on MTZ2 and MTZ3 frames.

Drawout mounting means this release plugs into the MasterPact MTZ cradle — no hard wiring to the breaker itself. The signalling function (coil powered MN open error) gives a remote indication that the undervoltage coil is energized and the breaker is ready to close, or that a trip has occurred. For a safety circuit, this diagnostic output lets a PLC or safety relay confirm the breaker state without adding auxiliary contacts.

Frequently asked questions

What is the closest alternative to LV839268 in this component family?

No official successor order code is recorded for the LV839268. The replacement may involve a different release family or a cradle adapter for the MasterPact MTZ drawout frame. A direct cross-reference is not available from the manufacturer.

MPN
LV839268