Skip to main content
Schneider Electric LV839309 — Air Circuit Breakers

Schneider Electric LV839309 Masterpact MTZ3 40 HA, 4000A, 65

MPNLV839309
Active

Schneider Electric Masterpact MTZ3 40 HA, LV839309, switch disconnector, 4000 A, 65 kA Icu, 3P, drawout, chassis mount.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839309 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839309 — Electrical ratings
ParameterValue
Rated operational current (Ie)4000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839309 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)65.0 kA 0.5 s ANSI C37.50
Breaking capacity65.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839309 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width31.07 in (789.1 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)

Product details

The Schneider Electric LV839309 is a Masterpact MTZ3 40 HA automatic switch disconnector, rated 4000 A at 104 °F (40 °C) for distribution duty. It's a 3-pole drawout unit on a chassis mount, controlled via push-button, and built for AC networks at 50/60 Hz.

Breaking capacity and withstand — the real coordination numbers

The LV839309 delivers 65.0 kA Icu at 254 V, 508 V, and 635 V AC (50/60 Hz) with an external relay per ANSI C37.50. That's a flat 65 kA across the common distribution voltages — no derating curve to chase. The rated short-time withstand current [Icw] is also 65.0 kA for 0.5 s per ANSI C37.50, which means it holds through a delayed trip without welding contacts. For a site electrical engineer building a selective coordination study, that Icw match to Icu simplifies the upstream breaker choice — you don't need a bigger gap between the two.

The drawout mechanism and chassis mount mean the LV839309 is designed for a fixed switchgear lineup, not a DIN-rail panel. Depth is 16.8 in (426.8 mm), width 31.07 in (789.1 mm), height 18.8 in (478.1 mm). Connection pitch is 9.06 in (230 mm) — verify busbar spacing against your existing switchgear cubicle before committing the footprint. The drawout cradle stays in the cabinet; the breaker element racks in and out for maintenance without disturbing the line and load connections.

Frequently asked questions

What is the breaking capacity of the LV839309?

The LV839309 has a breaking capacity of 65.0 kA Icu at 254 V, 508 V, and 635 V AC (50/60 Hz) with an external relay, per ANSI C37.50. Its short-time withstand current [Icw] is also 65.0 kA for 0.5 s.

Where can I buy the LV839309?

The LV839309 is sourced and quoted to order against an RFQ through independent industrial automation distribution. Availability and current pricing are confirmed at quote time.

MPN
LV839309