Skip to main content
Schneider Electric LV839310 — Air Circuit Breakers

Schneider Electric LV839310 Masterpact MTZ3 50 HA, 5000 A, 3

MPNLV839310
Active

Schneider Electric Masterpact MTZ3 50 HA, switch disconnector, 5000 A, ANSI, 3P, drawout, ArcBlok, 65 kA Icu breaking capacity.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839310 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839310 — Electrical ratings
ParameterValue
Rated operational current (Ie)5000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839310 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)65.0 kA 0.5 s ANSI C37.50
Breaking capacity65.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 65.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839310 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width31.07 in (789.1 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)

Product details

The LV839310 is a Masterpact MTZ3 50 HA switch disconnector rated for 5000 A at 104 °F (40 °C), with a 65 kA Icu breaking capacity across 254 V, 508 V, and 635 V AC 50/60 Hz per ANSI C37.50. The 65 kA Icw short-time withstand (0.5 s) lets it ride through a delayed trip without damage, so you can coordinate with downstream feeders. The drawout chassis mounting means the breaker can be racked out for maintenance or replacement without de-energizing the bus — a standard requirement for main and tie breakers in switchgear.

The drawout mounting and chassis support place this breaker in a metal-enclosed low-voltage switchgear lineup — ANSI-rated, typically for main, tie, or large feeder positions. The 3-pole configuration with push-button control suits distribution applications where remote or local switching is needed. ArcBlok technology is integral to the arc chamber design, reducing arc energy during interruption and extending contact life.

Frequently asked questions

Where can I buy LV839310 and how is it quoted?

The LV839310 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of LV839310?

The LV839310 has a 65 kA Icu breaking capacity at 254 V, 508 V, and 635 V AC 50/60 Hz with external relay per ANSI C37.50, and a 65 kA Icw short-time withstand current for 0.5 s per ANSI C37.50.

What is the rated current of LV839310?

The LV839310 has a rated operational current of 5000 A at 104 °F (40 °C).

MPN