Schneider Electric LV839313 — Air Circuit Breakers

LV839313 Masterpact MTZ3 40 HF Switch Disconnector, 4000 A,

MPNLV839313
Active

Schneider Electric Masterpact MTZ3 40 HF switch disconnector, LV839313, 4000 A, 100 kA Icu at 254 V AC, 3P drawout, ArcBlok.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV839313 — Identification
ParameterValue
Product typeSwitch disconnector
ApplicationDistribution

Electrical ratings

LV839313 — Electrical ratings
ParameterValue
Rated operational current (Ie)4000 A 104 °F (40 °C)
Poles3P
Network typeAC
Network frequency50/60 Hz

Breaking & withstand capacity

LV839313 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85.0 kA 1.5 s ANSI C37.50
Breaking capacity100.0 kA Icu 254 V AC 50/60 Hz with external relay ANSI C37.50 100.0 kA Icu 508 V AC 50/60 Hz with external relay ANSI C37.50 85.0 kA Icu 635 V AC 50/60 Hz with external relay ANSI C37.50

Mechanical & connection

LV839313 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Width31.07 in (789.1 mm)
Height18.8 in (478.1 mm)
Depth16.8 in (426.8 mm)
Connection pitch9.06 in (230 mm)

Product details

The Schneider Electric LV839313 is a Masterpact MTZ3 40 HF automatic switch disconnector rated 4000 A at 104 °F (40 °C) in a 3-pole drawout chassis mount. It's built for distribution duty — the kind of main or feeder disconnect you spec into a switchboard where you need to isolate a 4000 A bus without pulling the whole assembly.

The 100 kA Icu at 254 V AC (and 85 kA at 635 V AC) tells you the interrupting capacity at the line side; the 85 kA Icw for 1.5 s is the short-time withstand — it holds that fault current long enough for downstream breakers to clear, which is what makes selective coordination possible. Both figures are with an external relay per ANSI C37.50, so the relay choice affects the rating.

Mounting and physical integration

Drawout mounting means the moving portion slides out of the chassis for inspection or swap without disturbing the bus connections — no crane, no unbolting heavy lugs. The chassis mount itself bolts into the switchboard frame. Overall footprint: 31.07 in wide, 18.8 in tall, 16.8 in deep, with a 9.06 in connection pitch. Push-button control on the front for local open/close. Plan for the depth when laying out the enclosure door swing.

Active in production per the manufacturer's lifecycle status.

Frequently asked questions

What is the breaking capacity of LV839313?

100 kA Icu at 254 V AC 50/60 Hz with an external relay per ANSI C37.50, 100 kA at 508 V, and 85 kA at 635 V. Short-time withstand is 85 kA for 1.5 s.

MPN