Skip to main content
Schneider Electric LV846162 — Air Circuit Breakers

Schneider LV846162 MasterPact MTZ2 1250A 3P Circuit Breaker,

MPNLV846162
Active

Schneider Electric MasterPact MTZ2, fixed circuit breaker, 3P, 1250 A at 40 °C, H2V 100 kA at 415 V AC, push-button control, without control unit.

$4,037.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV846162 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
RangeMasterPacT
ApplicationPower distribution protection
Control unitWithout control unit
LV846162 — Electrical ratings
ParameterValue
Rated current (In)1250 A at 40 °C
Sensor rating630 A 800 A 1000 A 1250 A
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2
LV846162 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated service breaking capacity (Ics)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated short-time withstand current (Icw)100 kA 0.5 s 100 kA 1 s 75 kA 3 s
Rated short-circuit making capacity (Icm)220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz
Performance typeH2V 100 kA 415 V AC
LV846162 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)15000 cycles with periodic preventive maintenance
Electrical durability (cycles)10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Selectivity categoryCategory B
Power dissipation100 W
LV846162 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width422 mm
Height352 mm
Depth300 mm
Connection pitch115 mm
Upside connectionFront Rear
Downside connectionFront Rear
LV846162 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating altitude0...2000 m without derating 2000...5000 m with derating
LV846162 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The Schneider LV846162 is a MasterPact MTZ2 fixed-mount circuit breaker, 3-pole, rated 1250 A at 40 °C. It belongs to the H2V performance tier — 100 kA ultimate breaking capacity (Icu) at 440 V AC, 50/60 Hz, and the same 100 kA service breaking (Ics). That means it clears a fault up to 100 kA and stays functional afterward, no immediate replacement needed. Category B selectivity (per EN/IEC 60947-2) lets it coordinate with downstream breakers so only the faulted branch trips — critical for a production line where you want the main breaker to hold while a feeder clears. Rated operational voltage is 440 V AC, insulation voltage 1000 V AC, impulse withstand 12 kV. Short-time withstand (Icw) holds 100 kA for 0.5 s and 1 s, 75 kA for 3 s — enough for selective coordination with downstream devices. Mounting is fixed on rails or base plate, connection pitch 115 mm. Both upside and downside connections accept front or rear terminations — common in switchboard builds where cable routing differs between incoming and outgoing sections. IP30 protection; inside a panel that's fine, but keep it out of direct washdown zones.

Also meets IEC 61557-12 for insulation monitoring. Isolation suitability is confirmed per EN/IEC 60947-2 — the breaker provides visible isolation when open. Altitude derating above 2000 m is specified, so check if your installation is above that.

Frequently asked questions

What is LV846162's rated breaking capacity?

The LV846162 has an Icu of 100 kA at 440 V AC and an Ics of 100 kA at 440 V AC — full-rated service breaking. Icm is 220 kA at 440 V AC.

What compliance documentation does Schneider provide for LV846162?

The LV846162 complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2.

MPN
LV846162