Skip to main content
Schneider Electric LV846170

LV846170 MasterPact MTZ2 800A Circuit Breaker, 100 kA

MPN LV846170
Active

Schneider Electric MasterPacT MTZ2, LV846170, drawout circuit breaker, 3P, 800 A at 40 °C, H2V 100 kA at 415 V AC, EN/IEC 60947-2.

$3,447.90 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846170 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846170 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width441 mm
Height439 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV846170 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 800 A at 40 °C. It belongs to the H2V performance class, delivering 100 kA ultimate breaking capacity (Icu) at 440 V AC — the same figure holds for service breaking (Ics), so it clears a fault and is ready to reclose without derating the installation. The making capacity (Icm) is 220 kA at 440 V, meaning it can close onto a bolted fault without welding contacts. Short-time withstand (Icw) is 100 kA for 1 s, which supports full selectivity with downstream breakers in a distribution panel. This is a Category B breaker per IEC 60947-2, designed for power distribution protection in switchboards and industrial main feeders. The drawout chassis lets you rack the breaker out for maintenance or replacement without disturbing the bus connections — a standard requirement for low-voltage main and tie positions.

Because the Ics equals the Icu at both 220/415 V and 440 V, you don't lose capacity after a fault — the breaker stays in service without needing immediate replacement. That matters for critical feeders where downtime for breaker swap is unacceptable. The making capacity of 220 kA peak ensures the contacts close against the full asymmetrical fault current without arcing damage. Short-time withstand (Icw) of 100 kA for 1 s supports zone-selective interlocking and cascading schemes. With a maximum break time of 25 ms and closing response of 70 ms, this breaker coordinates cleanly with upstream and downstream devices in a selective coordination study.

Dimensions are 441 mm wide × 439 mm high × 403 mm deep. The drawout mechanism mounts on rails or a base plate; connection pitch is 115 mm. Both front and rear connection are supported on the upside and downside, giving flexibility for cable or busbar entry in a switchboard lineup. Altitude derating applies above 2000 m.

The breaker ships without a control unit — the Micrologic trip unit is ordered separately based on the protection profile needed (LSIG, LS, etc.). Sensor ratings of 400 A, 630 A, and 800 A are listed, meaning the breaker frame accepts interchangeable rating plugs to match the load without changing the power poles.

MPN
LV846170