Skip to main content
Schneider Electric LV846204 — Air Circuit Breakers

LV846204 MasterPact MTZ2 4P 2000A Circuit Breaker, 100 kA

MPNLV846204
Active

Schneider Electric MasterPacT range, MasterPact MTZ2 fixed circuit breaker, LV846204, 4P, 2000 A at 40 °C, H2V 100 kA at 415 V AC, IP30.

$7,898.04Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV846204 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
RangeMasterPacT
ApplicationPower distribution protection
Control unitWithout control unit

Electrical ratings

LV846204 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Sensor rating1000 A 1250 A 1600 A 2000 A
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2

Breaking & withstand capacity

LV846204 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated service breaking capacity (Ics)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated short-time withstand current (Icw)100 kA 0.5 s 100 kA 1 s 75 kA 3 s
Rated short-circuit making capacity (Icm)220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz
Performance typeH2V 100 kA 415 V AC

Performance

LV846204 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)15000 cycles with periodic preventive maintenance
Electrical durability (cycles)8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 8000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Selectivity categoryCategory B
Power dissipation250 W

Mechanical & connection

LV846204 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm
Neutral pole positionRight
Connection pitch115 mm
Upside connectionFront Rear
Downside connectionFront Rear

Environmental

LV846204 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating altitude0...2000 m without derating 2000...5000 m with derating

Approvals

LV846204 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The LV846204 is a fixed-mount MasterPact MTZ2 air circuit breaker from the MasterPacT range, rated 2000 A at 40 °C (In) with a 4-pole configuration (4P). Its H2V performance class delivers 100 kA Ics at 440 V AC — the service breaking capacity that governs real fault clearing without replacement. Category B selectivity means it coordinates downstream breakers to isolate only the faulted branch, keeping the rest of the distribution live. The 100 kA Icw for 1 second confirms it withstands a delayed trip coordination window, essential for selective schemes in industrial switchgear. The 2000 A frame is sized for main incoming feeders or large bus risers in power distribution. Fixed mounting on rails or base plate means it bolts into a dedicated cubicle — not a draw-out cradle — so panel layout and bus connections are permanent. Front and rear connection options give flexibility for cable or busbar entry.

The IP30 enclosure protects against tools and wires >2.5 mm but is not sealed against water — install in a dry cubicle or add an enclosure for washdown areas.

Environmental and durability ratings

Altitude derating applies above 2000 m. Mechanical durability is 15,000 cycles with periodic preventive maintenance; electrical durability is 8000 cycles at In under AC-23A. Maximum breaking time is 25 ms, closing response 70 ms. Power dissipation at rated current is 250 W — factor into cubicle ventilation calculations.

Frequently asked questions

Where can I buy LV846204 and how is it quoted?

The LV846204 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. Submit an RFQ for a firm price and lead time.

What is the breaking capacity of LV846204?

The rated service breaking capacity (Ics) is 100 kA at 440 V AC 50/60 Hz. The rated ultimate breaking capacity (Icu) for the H2V class is 100 kA at 415 V AC. The short-time withstand (Icw) is 100 kA for 1 second.

What compliance documentation does LV846204 carry?

The breaker complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2. Pollution degree 3 per IEC 60947-1.

MPN