Skip to main content
Schneider Electric LV846205 — Air Circuit Breakers

Schneider Electric LV846205 MasterPact MTZ2 2500 A Circuit B

MPNLV846205
Active

Schneider Electric MasterPact MTZ2, LV846205, 4P fixed circuit breaker, 2500 A at 40 °C, H2V 100 kA at 415 V AC, depth 300 mm, width 537 mm, height 352 mm.

$11,057.04Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV846205 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact MTZ2
RangeMasterPacT
ApplicationPower distribution protection
Control unitWithout control unit

Electrical ratings

LV846205 — Electrical ratings
ParameterValue
Rated current (In)2500 A at 40 °C
Sensor rating1250 A 1600 A 2000 A 2500 A
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2

Breaking & withstand capacity

LV846205 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated service breaking capacity (Ics)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz
Rated short-time withstand current (Icw)100 kA 0.5 s 100 kA 1 s 75 kA 3 s
Rated short-circuit making capacity (Icm)220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz
Performance typeH2V 100 kA 415 V AC

Performance

LV846205 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)15000 cycles with periodic preventive maintenance
Electrical durability (cycles)5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Selectivity categoryCategory B
Power dissipation260 W

Mechanical & connection

LV846205 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm
Neutral pole positionRight
Connection pitch115 mm
Upside connectionFront Rear
Downside connectionFront Rear

Environmental

LV846205 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating altitude0...2000 m without derating 2000...5000 m with derating

Approvals

LV846205 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The Schneider Electric LV846205 is a MasterPact MTZ2 4-pole fixed circuit breaker rated 2500 A at 40 °C, built for power distribution protection in industrial switchgear. Category B selectivity (per EN/IEC 60947-2) confirms it coordinates with downstream breakers so only the faulted branch clears.

Rated operational voltage is 440 V AC, with insulation rated 1000 V AC and impulse withstand at 12 kV — this breaker handles standard 400 V class distribution without derating. The Ics (service breaking capacity) matches the Icu at 100 kA for 440 V AC, so you get full rated performance after a fault event, not a reduced service rating. Short-time withstand (Icw) holds 100 kA for 0.5 s and 75 kA for 3 s, giving downstream protection devices time to clear before the main trips.

Fixed-mount design, 537 mm wide × 352 mm high × 300 mm deep. Mounts on rails or a base plate in the switchgear enclosure. Connection pitch is 115 mm; both front and rear connections are available on the upside and downside, giving flexibility for cable or busbar entry. The neutral is on the right side. IP30 protection means it's suitable for indoor panel installation where tools are required to access live parts.

Environmental and operational limits

Altitude rating is 0-2000 m without derating, 2000-5000 m with derating — factor that in for high-altitude installations. Power dissipation is 260 W at rated current, so enclosure cooling needs to account for that heat load.

Durability and mechanical life

Mechanical durability is 15,000 cycles with periodic preventive maintenance. Electrical durability is 5,000 cycles at In under AC-23A (440 V), and 6,000 cycles under AC-3. Maximum breaking time is 25 ms, closing response time 70 ms — fast enough for most distribution protection schemes.

Frequently asked questions

How do I get current pricing and availability for LV846205?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and current pricing are confirmed at quote time.

What is LV846205's listed depth?

The depth is 300 mm, with width 537 mm and height 352 mm.

What compliance documentation does this breaker carry?

It complies with EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. Suitability for isolation is confirmed per EN/IEC 60947-2.

What is the closest alternative to LV846205 in the MasterPact family?

Within the MasterPact MTZ2 range, the LV846205 is the 2500 A, 4P, H2V 100 kA fixed variant. A lower-current sibling (e.g., 2000 A) or a different performance class (e.g., H1) would differ in frame rating or breaking capacity — match the exact In and Icu for your coordination study.

MPN