Skip to main content
Schneider Electric LV846206

Schneider Electric LV846206 MasterPact MTZ2, 3200 A, 100 kA

MPN LV846206
Active

Schneider Electric MasterPact MTZ2, LV846206, fixed-mount circuit breaker, 4P, 3200 A at 40 °C, H2V 100 kA at 415 V AC, IP30.

$14,611.32 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846206 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846206 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The Schneider Electric LV846206 is a MasterPact MTZ2 fixed-mount air circuit breaker, 4-pole, rated 3200 A at 40 °C. It's built for main switchboard and large distribution protection — the kind of gear that sits on a base plate or rails in a utility or industrial substation, not a panelboard. It's Category B selectivity per IEC 60947-2, so you can coordinate it downstream without sacrificing uptime on a fault.

The 100 kA Ics at 440 V AC is the service breaking capacity — the breaker clears that fault and is still usable afterward, not just a one-shot Icu. The Icw is 100 kA for 1 second, which gives you real headroom for short-time delay coordination with downstream feeders. That 75 kA for 3 seconds matters if your protection scheme needs a longer clearing window. Insulation voltage Ui is 1000 V AC, impulse withstand Uimp is 12 kV — this breaker is rated for the heavy end of low-voltage distribution.

Fixed-mount version — no draw-out cradle. The 537 mm width, 352 mm height, and 300 mm depth give you the envelope for a dedicated cell in a switchboard. Connection pitch is 115 mm, and both front and rear connections are available for the upside and downside. Neutral is on the right.

Durability and thermal budget

Mechanical durability is 15,000 cycles with periodic preventive maintenance — that's typical for a main breaker that sees infrequent switching. Electrical durability at rated current is 5,000 cycles at 440 V AC under AC-23A duty. Power dissipation is 420 W at full load, so factor that into your switchgear ventilation. Altitude derating above 2000 m is specified.

MPN
LV846206