Skip to main content
Schneider Electric LV846318 — Air Circuit Breakers

Schneider Electric LV846318 MasterPact MTZ2 20HH Switch Disc

MPNLV846318
Active

Schneider Electric MasterPact MTZ2 20HH switch disconnector, LV846318, 2000A rated operational current, 3P drawout, 100 kA Icu at 440 V AC.

$5,420.52Ref. price · indicative, final on quote
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV846318 — Identification
ParameterValue
Product typeSwitch disconnector
RangeMasterPact
ApplicationDistribution

Electrical ratings

LV846318 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated operational current (Ie)2000 A AC 50/60 Hz 440 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to EN/IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to EN/IEC 60947-3

Breaking & withstand capacity

LV846318 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)100 kA at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated short-time withstand current (Icw)75 kA during 3 s conforming to EN/IEC 60947-3 100 kA during 1 s conforming to EN/IEC 60947-3
Rated short-circuit making capacity (Icm)220 kA peak 220/415 V AC at 50/60 Hz 220 kA peak 440 V AC at 50/60 Hz
Breaking capacity100 kA Icu at 220/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2

Performance

LV846318 — Performance
ParameterValue
Mechanical durability (cycles)15000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-3
Electrical durability (cycles)AC-23A: 8000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3
Utilisation categoryAC-23A AC-3

Mechanical & connection

LV846318 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Contact position indicatorYes
Width441 mm
Height439 mm
Depth403 mm
Connection pitch115 mm

Environmental

LV846318 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to EN/IEC 60947-4-1

Approvals

LV846318 — Approvals
ParameterValue
StandardsEN/IEC 60947-3

Product details

The LV846318 is a MasterPact MTZ2 20HH switch disconnector rated for 2000 A continuous current at 440 V AC — that's the full-load current it carries without exceeding temperature rise limits, sized for a main feeder or a large distribution bus. The drawout chassis lets you rack the unit out for inspection or swap without de-energizing the bus, which cuts downtime on a critical feeder.

Drawout integration and isolation duty

Mounts on a dedicated chassis with a 115 mm connection pitch — the drawout mechanism engages the primary disconnects as you rack in, and the contact position indicator confirms the blade state visually. Rated for isolation per EN/IEC 60947-3, so it provides a visible-break-equivalent gap when racked to the test or disconnected position.

Frequently asked questions

What is LV846318's rated breaking capacity at 440 V?

100 kA Icu at 440 V AC 50/60 Hz per EN/IEC 60947-2, with matching 100 kA Ics for full service continuity after fault clearance.

MPN