Skip to main content
Schneider Electric LV847260 — Air Circuit Breakers

LV847260 MasterPact MTZ2 08 HA10, 800A, 3P, Fixed Switch-Dis

MPNLV847260
Active

Schneider Electric MasterPact MTZ2 08 HA10 switch-disconnector, LV847260, 800 A rated operational current, 1150 V AC, 3 poles, fixed mounting, 105 kA peak short-circuit making capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV847260 — Identification
ParameterValue
Product typeSwitch disconnector
RangeMasterPact
ApplicationDistribution
LV847260 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated operational current (Ie)800 A AC 50/60 Hz 1150 V
Poles3P
Rated insulation voltage (Ui)1250 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to EN/IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to EN/IEC 60947-3
LV847260 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to EN/IEC 60947-3 50 kA during 3 s conforming to EN/IEC 60947-3
Rated short-circuit making capacity (Icm)105 kA peak 1150 V AC at 50/60 Hz
LV847260 — Performance
ParameterValue
Mechanical durability (cycles)25000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-3
Electrical durability (cycles)AC-23A: 500 cycles 1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Utilisation categoryAC-23A AC-3
LV847260 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Contact position indicatorYes
Width422 mm
Height352 mm
Depth300 mm
Connection pitch115 mm
LV847260 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to EN/IEC 60947-4-1
LV847260 — Approvals
ParameterValue
StandardsEN/IEC 60947-3

Product details

The LV847260 is a MasterPact MTZ2 08 HA10 switch-disconnector rated 800 A continuous at 1150 V AC, 50/60 Hz, with a short-circuit making capacity of 105 kA peak at that voltage. The 50 kA Icw for 1 s (and 3 s) means it holds through a delayed trip coordination, so it works with selective breaker schemes downstream. Rated insulation voltage is 1250 V, impulse withstand 12 kV — it's built for 690 V class systems with margin, or 1000 V industrial grids. Utilisation categories AC-23A and AC-3 cover switching of motor loads with occasional inrush (AC-3) and mixed resistive-inductive loads including occasional motor starting (AC-23A). The 800 A frame handles large motors, transformers, or main feeders. Fixed mounting, 3-pole, push-button control, no visible break — this is a panel-mounted disconnect, not a plug-in unit.

Deployment context

This switch-disconnector lives in a fixed-mount enclosure — typically a distribution panel or motor control centre. The 422 mm width, 352 mm height, and 300 mm depth tell you the cubicle cutout and backpanel space needed. IP30 protection means it's for indoor, clean environments; not washdown or outdoor without an enclosure.

Frequently asked questions

Where can I buy LV847260 and what is the lead time?

The LV847260 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or lead-time number is published here.

What is LV847260's short-circuit rating?

The LV847260 has a short-circuit making capacity (Icm) of 105 kA peak at 1150 V AC, and a short-time withstand (Icw) of 50 kA for 1 second and 3 seconds, all per EN/IEC 60947-3.

MPN