Schneider Electric LV847270 — Air Circuit Breakers

Schneider Electric LV847270 MasterPact MTZ2 08 HA10, 800 A,

MPNLV847270
Active

Schneider Electric MasterPact MTZ2 08 HA10 switch-disconnector, LV847270, 800 A, 105 kA/1150 VAC 50/60 Hz (Icm), 4P, fixed.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV847270 — Identification
ParameterValue
Product typeSwitch disconnector
RangeMasterPact
ApplicationDistribution
LV847270 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated operational current (Ie)800 A AC 50/60 Hz 1150 V
Poles4P
Rated insulation voltage (Ui)1250 V AC 50/60 Hz conforming to EN/IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to EN/IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to EN/IEC 60947-3
LV847270 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to EN/IEC 60947-3 50 kA during 3 s conforming to EN/IEC 60947-3
Rated short-circuit making capacity (Icm)105 kA peak 1150 V AC at 50/60 Hz
LV847270 — Performance
ParameterValue
Mechanical durability (cycles)25000 cycles with periodic preventive maintenance conforming to EN/IEC 60947-3
Electrical durability (cycles)AC-23A: 500 cycles 1150 V AC 50/60 Hz conforming to EN/IEC 60947-3
Utilisation categoryAC-23A AC-3
LV847270 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Contact position indicatorYes
Width537 mm
Height352 mm
Depth300 mm
Connection pitch115 mm
LV847270 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to EN/IEC 60947-4-1
LV847270 — Approvals
ParameterValue
StandardsEN/IEC 60947-3

Product details

The LV847270: The 800 A rated operational current (Ie) at 1150 V AC defines the continuous load this switch can carry in distribution duty. The 50 kA short-time withstand (Icw) for 1 s or 3 s lets it coordinate with downstream breakers during a fault-clearing delay. The AC-23A and AC-3 utilisation categories cover switching of motor loads and mixed resistive-inductive loads, not just passive distribution. Suitability for isolation per EN/IEC 60947-3 is confirmed, with a visible break indicator and a contact position indicator. The rated insulation voltage (Ui) of 1250 V AC and impulse withstand (Uimp) of 12 kV give headroom for 690 V or 1000 V systems. The fixed-mount form factor bolts directly into a panel; the 115 mm connection pitch matches standard busbar spacing for MasterPact drawout or fixed chassis.

Frequently asked questions

What are the key ratings of LV847270?

The LV847270 is rated 800 A operational current (Ie) at 1150 V AC, with a short-circuit making capacity (Icm) of 105 kA peak and short-time withstand (Icw) of 50 kA for 1 s or 3 s, all per EN/IEC 60947-3.

Where can I buy LV847270?

The LV847270 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider Electric provide for LV847270?

The LV847270 is certified to EN/IEC 60947-3 for switch-disconnectors, with suitability for isolation, pollution degree 3, and impulse withstand voltage of 12 kV per that standard.

MPN
LV847270