Schneider Electric LV847288WW — Air Circuit Breakers

Schneider Electric LV847288WW MicroLogic 6.0 Xi Control Unit

MPNLV847288WW
Active

Schneider Electric MasterPacT MicroLogic 6.0 Xi electronic control unit, LV847288WW, LSIG protection, LCD display, 3P/4P, wired control, fixed mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV847288WW — Identification
ParameterValue
Product typeControl unit
RangeMasterPacT
ApplicationEquipment protection, monitoring and control
LV847288WW — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC, +/- 10 %
Network typeAC
Network frequency50/60 Hz
LV847288WW — Mechanical & connection
ParameterValue
Control typeWired control
Mounting modeFixed
LV847288WW — Environmental
ParameterValue
Operating ambient temperature-25...70 °C (operating) -35 °C (for start-up of product)
Pollution degree3 conforming to IEC 60947-1
Operating altitude<= 5000 m with operational voltage derating 560 V AC
LV847288WW — Approvals
ParameterValue
StandardsEN/IEC 60255-1 EN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 61010-1

Product details

What this control unit does

The Schneider Electric LV847288WW is a MicroLogic 6.0 Xi electronic control unit for MasterPacT circuit breakers. It provides LSIG protection — long-time and short-time overcurrent, instantaneous short-circuit, and earth fault — with adjustable time delays and thresholds. The unit also functions as a power meter, measuring voltage, current, power, energy, harmonics, and frequency across the network. Measurement voltage spans 208...828 V AC phase-to-phase and 120...480 V AC phase-to-neutral. The trip unit is rated for currents from 400 A up to 6300 A, depending on the breaker frame (MTZ1/MTZ2/MTZ3). Accuracy is Class 0.5 for voltage and unbalance, Class 1 for active energy and power, Class 2 for THD(V), and Class 5 for THD(I). Current measurement accuracy is +/- 0.5% across the full range for all three frame sizes.

Protection and metering in one package

This unit combines protection relay and revenue-grade metering in a single control unit that mounts fixed inside the MasterPacT breaker. The LCD display (128 x 96 pixels) shows real-time values, event logs, alarm logs, and maintenance logs with time stamping. Thermal memory is included, so the unit tracks heat buildup across overload events. Zone selective interlocking (ZSI) is supported, allowing multiple breakers in a distribution system to coordinate trip timing and reduce arc-flash energy. The unit communicates via USB peer-to-peer at 115 kbauds for local configuration and data retrieval. Overvoltage category IV per IEC 61010-1 confirms it can be installed at the service entrance or main distribution panel. Indoor use only; not approved for wet locations.

The LV847288WW complies with EN/IEC 60255-1 (measuring relays), EN/IEC 60947-2 (circuit breakers), EN/IEC 60092-202 (marine electrical), EN/IEC 60947-1 (low-voltage switchgear), and EN/IEC 61010-1 (safety requirements for electrical equipment). EMC immunity covers electrostatic discharge, radiated fields, fast transients, surge 1.2/50 µs, and conducted RF per IEC 61000-4-2 through -6. Conducted and radiated emissions meet Class A of CISPR 22.

Pole configurations and neutral protection

The control unit supports 3-pole and 4-pole breaker configurations. Protected pole options include 3P 3d, 4P 3d, 4P 3d + N/2, 4P 4d, and 4P 3d + OSN. Neutral protection settings are selectable: 1 x Ir (4P 4d), 0.5 x Ir (4P 3d + N/2), 1.6 x Ir (4P 3d + OSN), or no protection (4P 3d).

Frequently asked questions

What protection functions does the MicroLogic 6.0 Xi provide?

LSIG protection: overload (long time, ANSI 49), instantaneous short-circuit (ANSI 50), short-time short-circuit (ANSI 51), and earth fault (ANSI 51N). All are adjustable.

What is the measurement accuracy of this control unit?

Current accuracy is +/- 0.5% for all three frame sizes. Voltage accuracy is +/- 0.5%. Active power and energy are +/- 1%. Reactive power and energy are +/- 2%. Frequency accuracy is +/- 0.005 Hz.

Where can I buy LV847288WW?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does LV847288WW comply with?

It complies with EN/IEC 60255-1, EN/IEC 60947-2, EN/IEC 60092-202, EN/IEC 60947-1, and EN/IEC 61010-1. EMC per IEC 61000-4-2 through -6 and CISPR 22 Class A.

MPN
LV847288WW