Schneider Electric LV847411 — Air Circuit Breakers

LV847411 MasterPact MTZ1 Voltage Release, 12 VDC, Obsolete

MPNLV847411
Obsolete

Schneider Electric MasterPact MTZ1 drawout, XF closing voltage release with diagnostics & communication, 12 VDC, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV847411 — Identification
ParameterValue
Product typeVoltage release
RangeMasterPact
ApplicationControl
LV847411 — Mechanical & connection
ParameterValue
Control typeCommunicating
LV847411 — Other specifications
ParameterValue
Device short nameXF diag & com
Signalling functionError Electrical push-button activated Coil powered Ready to close or open
Voltage release typeClosing coil
Maximum response time65 ms on closing MasterPact MTZ1
Holding power consumption4.5 W
[Un] voltage power supply12 V DC
Threshold tripping voltage0.85...1.1 Un on closing
Circuit breaker mounting modeDrawout

Product details

LV847411 is a Schneider Electric MasterPact MTZ1 drawout closing voltage release (XF diag & com type) that operates on a 12 VDC supply. It signals error, electrical push-button activation, coil power, and ready-to-close/open status. Maximum response time is 65 ms on closing for MasterPact MTZ1 frames.

The 12 VDC supply (0.85–1.1 Un on closing threshold) matches low-voltage control schemes common in industrial panels where a separate 12 VDC bus powers trip/close coils. Holding power consumption of 4.5 W keeps the burden on the DC supply modest. The 65 ms max response time on MTZ1 drawout breakers is fast enough for most coordination schemes — selectivity curves are unaffected at this closing speed.

Deployment Context

Designed for drawout MasterPact MTZ1 circuit breakers — the communicating variant integrates with building management or SCADA systems via the XF diagnostics interface. Mounted inside the breaker cradle, it replaces the standard closing coil when remote status and diagnostics are required.

Frequently asked questions

How do I get current pricing and availability for LV847411?

Pricing and stock are confirmed at quote time against an RFQ. Because the part is obsolete, availability varies — we check our multi-source network on each request.

What is LV847411's listed range (MasterPact) on this component line?

The range is MasterPact — specifically the MTZ1 drawout frame. This is the communicating closing voltage release variant (XF diag & com).

What is LV847411's listed control type (Communicating) on this component line?

Control type is Communicating — the XF variant includes diagnostics and communication functions alongside the closing coil, enabling remote status monitoring.

MPN
LV847411