Skip to main content
Schneider Electric LV847604 — Air Circuit Breakers

Schneider LV847604 MicroLogic 7.0 X Control Unit, MasterPacT

MPNLV847604
Active

Schneider Electric MasterPacT MicroLogic 7.0 X control unit, LV847604, electronic trip unit with LSIV protection, LCD display, 4P 3P poles, rated for 400–3200 A frames.

$5,896.07Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV847604 — Identification
ParameterValue
Product typeControl unit
RangeMasterPacT
ApplicationEquipment protection, monitoring and control
LV847604 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)600 V AC, +/- 10 %
Network typeAC
Network frequency50/60 Hz
LV847604 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C (operating) -35 °C (for start-up of product)
Pollution degree3 conforming to IEC 60947-1
Operating altitude<= 5000 m with operational voltage derating 560 V AC
LV847604 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60092-202 EN/IEC 60255-1 EN/IEC 60947-2 EN/IEC 61010-1

Product details

What this control unit does

The LV847604 is a MicroLogic 7.0 X electronic control unit for Schneider MasterPacT circuit breakers. It's the brain that handles equipment protection, monitoring, and control inside the breaker — not a standalone device. You slot it into a compatible MasterPacT frame (trip unit ratings from 400 A up to 3200 A) and it takes over the trip logic, metering, and communications. Protection functions are LSIV: long-time overload (ANSI 49), instantaneous short-circuit (ANSI 50), short-time short-circuit (ANSI 51), and earth-leakage (ANSI 51G). That covers the full selectivity stack for a distribution feeder — you can coordinate downstream breakers with the short-time delay and ZSI (zone selective interlocking) to clear faults fast without tripping the whole bus. It measures everything you'd expect from a power meter: per-phase and average RMS current, neutral and ground fault current, phase-to-phase and phase-to-neutral voltage, active/reactive/apparent power, power factor, energy in/out/total, frequency, THD for current and voltage, unbalance, and demand values. Accuracy on current and voltage is ±0.5 %, active energy ±1 % — Class 1 for billing-grade energy logging.

Mounts inside the MasterPacT breaker — no DIN rail, no separate enclosure. The 128 x 96 pixel LCD gives you local readout of all metered values and event logs without needing to plug in a laptop. Communication ports are Bluetooth 4.0 LE (30 kbit/s), NFC (28.8 kbaud), and USB (115 kbaud) for local configuration and data pull. No onboard Ethernet or fieldbus — that comes via a separate communication module on the breaker. Indoor use only, wet locations not approved. Operating altitude up to 5000 m with voltage derating above 2000 m (560 V AC at max altitude).

Frequently asked questions

What protection functions does LV847604 provide?

LSIV: long-time overload (ANSI 49), instantaneous short-circuit (ANSI 50), short-time short-circuit (ANSI 51), and earth-leakage (ANSI 51G). It also includes zone selective interlocking (ZSI) for coordinated fault clearing.

What trip unit ratings are compatible with LV847604?

It's designed for MasterPacT frames with trip unit ratings of 400 A, 630 A, 800 A, 1000 A, 1250 A, 1600 A, 2000 A, 2500 A, and 3200 A. The control unit itself doesn't set the rating — it adapts to the breaker frame's current sensor.

What compliance standards does LV847604 meet?

Certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60092-202 (marine), EN/IEC 60255-1, and EN/IEC 61010-1. EMC compliance per IEC 61000-4-2/3/4/5/6 and CISPR 22 Class A conducted/radiated emissions.

Where can I buy LV847604 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

MPN
LV847604