Schneider Electric LV847609 — Air Circuit Breakers

Schneider LV847609 MicroLogic 5.0 X, MasterPacT trip unit, L

MPNLV847609
Active

Schneider Electric MasterPacT range, MicroLogic 5.0 X electronic control unit, 4P 3P, LSI protection, LCD display, 690 V AC, 50/60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV847609 — Identification
ParameterValue
Product typeControl unit
RangeMasterPacT
ApplicationEquipment protection, monitoring and control
LV847609 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC, +/- 10 %
Network typeAC
Network frequency50/60 Hz
LV847609 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C (operating) -35 °C (for start-up of product)
Pollution degree3 conforming to IEC 60947-1
Operating altitude<= 5000 m with operational voltage derating 560 V AC
LV847609 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 60255-1

Product details

Control unit for MasterPacT breakers — what it does and what to check

The Schneider Electric LV847609 is a MicroLogic 5.0 X electronic control unit for the MasterPacT range of air circuit breakers. It provides LSI protection (long-time, short-time, instantaneous) plus comprehensive power metering and diagnostics, all via a 128 x 96 pixel LCD display. The trip unit supports multiple sensor ratings from 400 A up to 6000 A (the listed range includes 400 A, 600 A, 800 A, 1000 A, 1200 A, 1600 A, 2000 A, 2500 A, 3000 A, 3200 A, 3600 A, 4000 A, 5000 A, and 6000 A). Pole configuration is 4P 3d (three protected poles, one neutral), with options for 4P 4d, 4P 3d + N/2, and 4P 3d + OSN. Neutral protection is selectable per those configurations.

LSI protection covers overload (long-time, adjustable 0.4–1 x In in 1 A steps), short-time (adjustable delay 0–0.4 s with I²t on/off), and instantaneous short-circuit. Zone selective interlocking (ZSI) is included — this lets multiple breakers in a cascade communicate fault location, reducing stress on upstream gear during a downstream fault. Metering covers all standard electrical parameters: per-phase and average voltage (phase-to-phase and phase-to-neutral), current (I1, I2, I3, Iavg, neutral, ground fault), active/reactive/apparent power and energy, power factor, frequency, THD for current and voltage, unbalance, and demand values. Accuracy is ±0.5 % for current and voltage, ±1 % for active power and energy, ±2 % for reactive quantities. Communication ports include Bluetooth 4.0 LE (30 kbit/s), NFC (28800 baud), and USB (115 kbaud). The unit logs maintenance events, alarms, min/max values, and trip context — useful for post-fault analysis without a separate data logger.

Lifecycle and sourcing — current production, quoted to order

Standards compliance includes EN/IEC 60947-2 (circuit breakers), EN/IEC 60092-202 (marine electrical installations), EN/IEC 60947-1 (general rules), and EN/IEC 60255-1 (measuring relays).

Frequently asked questions

Where can I buy LV847609 and how do I get a price?

The LV847609 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm availability and current pricing.

What is LV847609's listed poles (4P 3P) on this component line?

The LV847609 is listed as 4P 3P (four poles, three protected poles plus neutral). It supports multiple neutral protection configurations: 4P 4d, 4P 3d + N/2, 4P 3d + OSN, and no protection (4P 3d).

What compliance documentation does this brand provide for LV847609?

The LV847609 complies with EN/IEC 60947-2, EN/IEC 60092-202, EN/IEC 60947-1, and EN/IEC 60255-1. It also meets pollution degree 3 per IEC 60947-1 and EMC requirements per IEC 61000-4-2 through -4-6 and CISPR 22 Class A.