Skip to main content
Schneider Electric LV848103 — Circuit Breaker Accessories

Schneider Electric LV848103 MasterPact MTZ3 4000 A Circuit B

MPNLV848103
Active

Schneider Electric MasterPact MTZ3, LV848103, fixed 4P circuit breaker, 4000 A at 40 °C, H2 performance 150 kA at 415 V AC, rear connection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LV848103 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ3
Product rangeMasterPacT
Device applicationPower distribution protection
LV848103 — Electrical
ParameterValue
Rated current [In]4000 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P
LV848103 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]150 kA at 220/415 V AC 50/60 Hz 150 kA at 440 V AC 50/60 Hz 130 kA at 500/525 V AC 50/60 Hz 100 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability10000 cycles with periodic preventive maintenance
Electrical durabilityAC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 1500 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 1500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 1500 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 1500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3
LV848103 — Mechanical
ParameterValue
Connection pitch230 mm
Downside connectionRear
Upside connectionRear
Device short nameMTZ3 40 H2
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width997 mm
Height352 mm
Depth300 mm
LV848103 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C
LV848103 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The Schneider Electric LV848103 is a MasterPact MTZ3 fixed-mount circuit breaker, 4 poles, rated 4000 A at 40 °C. Rear connection top and bottom, so it's built for switchboard bus-stack integration, not standalone panel mounting.

Category B selectivity means this breaker is designed for full discrimination with downstream devices — a fault on a branch won't take the main feeder out. The Icw short-time withstand is 100 kA for up to 3 seconds, which gives downstream breakers time to clear before the main trips. That's the spec that matters for coordination studies in a distribution board. Rated insulation voltage is 1000 V AC, operational voltage 690 V AC. Impulse withstand at 12 kV.

Physical fit

Fixed mounting on rails or base plate. Width 997 mm, height 352 mm, depth 300 mm. Connection pitch 230 mm. That depth is the overall front-to-back dimension including the mechanism — verify cabinet depth before specifying. Neutral position is right.

Standards and documentation

Compliant with EN/IEC 60947-1, EN/IEC 60947-2, and Annex H for selective coordination. Also meets IEC 61557-12 for power metering. Suitability for isolation confirmed per EN/IEC 60947-2. IP30 protection — not for washdown, but fine in a clean switchroom.

Frequently asked questions

What is the breaking capacity of LV848103?

H2 performance class: Ics service breaking capacity 150 kA at 220/415 V AC and 440 V AC, 130 kA at 500/525 V AC, 100 kA at 660/690 V AC. Icm making capacity 330 kA at 415 V.

Where can I buy LV848103?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
LV848103