Skip to main content
Schneider Electric LV848179

Schneider Electric LV848179 MasterPact MTZ2 4P 1250A Circuit

MPN LV848179
Active

Schneider Electric MasterPacT MTZ2, fixed circuit breaker, 4P, 1250 A at 40 °C, H2 100 kA 415 V AC, IP30, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848179 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848179 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23 A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3
Mechanical life cycles25000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ2 12 H2 — 1250 A fixed breaker for power distribution

The LV848179 is a Schneider Electric MasterPact MTZ2 fixed circuit breaker, 4 poles, rated 1250 A at 40 °C. The device is Category B selectivity, so it coordinates with downstream breakers to isolate only the faulted branch, keeping the rest of the distribution live.

The Icw short-time withstand is 85 kA for 1 second, which matters for coordination studies: downstream devices must clear within that window or the breaker's through-fault rating is exceeded. Rated impulse withstand voltage is 12 kV, covering surge events on industrial mains. The 100 W power dissipation at rated current means the panel's thermal budget needs to account for that heat — forced ventilation or larger enclosure volume may be required if other heat sources are nearby.

Mounting and integration — fixed, front/rear connections

Fixed mounting on rails or base plate. Connection pitch is 115 mm. Both upside and downside connections accept front or rear terminations, giving flexibility for panel layout — rear connection keeps cabling out of the door swing area. Neutral is on the right. Dimensions: 537 mm wide, 352 mm high, 300 mm deep — verify the enclosure depth allows rear cable bending radius.

This is a current-production part, so lead times are typically factory-build cycles rather than last-time-buy surplus.

MPN
LV848179