Schneider Electric LV848180 — Circuit Breaker Accessories

Schneider Electric LV848180 MasterPact MTZ2 1600 A Circuit B

MPNLV848180
Active

Schneider Electric MasterPact MTZ2, fixed circuit breaker, 4P, 1600 A at 40 °C, H2 100 kA at 415 V AC, push-button control, without control unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LV848180 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection
LV848180 — Electrical
ParameterValue
Rated current [In]1600 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P
LV848180 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 500/525 V AC 50/60 Hz 85 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability25000 cycles with periodic preventive maintenance
Electrical durability10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3
LV848180 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 16 H2
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm
LV848180 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C
LV848180 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The Schneider Electric LV848180 is a MasterPact MTZ2 fixed-mount circuit breaker, 4-pole, rated 1600 A at 40 °C, with an H2 performance class delivering 100 kA breaking capacity at 415 V AC. It's a Category B breaker (fully selective per EN/IEC 60947-2), meaning it coordinates with downstream devices to isolate only the faulted branch — critical for maintaining uptime on a plant distribution bus.

Rated operational voltage is 690 V AC, with an insulation voltage of 1000 V AC and impulse withstand of 12 kV — this breaker is built for 480/600 V class switchgear, not just 240 V panels. Short-time withstand (Icw) is 85 kA for 1 second, which is what lets it ride through a downstream fault and stay closed for selective coordination. Power dissipation is 170 W — plan for ventilation in the enclosure. Mechanical durability is 25,000 cycles with periodic preventive maintenance; electrical durability is 10,000 cycles at 440 V AC under EN/IEC 60947-2. For motor-switching duty (AC-3), it's rated 6,000 cycles at 440/690 V. Maximum break time is 25 ms, close time 70 ms — fast enough for most coordination schemes. This breaker ships without a control unit and uses push-button control. It accepts sensor ratings from 800 A through 1600 A, so you can fit it with a lower-rated sensor if the load doesn't need the full frame. Neutral is on the right. Mounting is fixed on rails or a base plate. Altitude rating is 0–2000 m without derating, 2000–5000 m with derating.

Frequently asked questions

How do I get current pricing and availability for LV848180?

Submit an RFQ for the LV848180. Pricing and stock are confirmed at quote time through independent distribution channels.

What is LV848180's rated current and breaking capacity?

The LV848180 is rated 1600 A at 40 °C with an H2 breaking capacity of 100 kA at 415 V AC. Service breaking capacity (Ics) is 100 kA at 440 V AC.

What compliance standards does LV848180 meet?

The LV848180 is certified to EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. It is suitable for isolation per EN/IEC 60947-2.

What is the closest alternative to LV848180 in the MasterPact family?

Within the MasterPact MTZ2 range, the LV848180 is the 4-pole, 1600 A, H2 (100 kA) fixed-mount variant. A lower-amp variant (e.g., 800 A frame) or a different performance class (H1, H3) would be a different order code. No direct pin-compatible alternative exists; the frame size and mounting pattern are specific to this rating.

MPN