Skip to main content
Schneider Electric LV848181 — Circuit Breaker Accessories

LV848181 MasterPact MTZ2 3200A Circuit Breaker, 100 kA

MPNLV848181
Active

Schneider Electric MasterPacT MTZ2, LV848181, fixed circuit breaker, 4P, 3200 A at 40 °C, H2 100 kA 415 V AC, push-button control, IP30.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV848181 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection

Electrical

LV848181 — Electrical
ParameterValue
Rated current [In]3200 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P

Protection & Performance

LV848181 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 500/525 V AC 50/60 Hz 85 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability20000 cycles with periodic preventive maintenance
Electrical durabilityAC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 2500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 5000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 2500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 5000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3

Mechanical

LV848181 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 32 H2
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm

Environmental

LV848181 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C

Approvals

LV848181 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

MasterPact MTZ2 3200 A — fixed-mount power breaker

The LV848181 is a Schneider Electric MasterPact MTZ2 fixed circuit breaker, 4-pole, rated 3200 A at 40 °C. Selectivity category B confirms it is designed for full discrimination downstream, critical for a main breaker in a distribution panel where you want only the faulted branch to trip.

Breaking performance and coordination

Rated short-time withstand current (Icw) is 85 kA for 0.5 s and 1 s, 75 kA for 3 s. That Icw figure governs the breaker's ability to hold a fault while downstream breakers clear — essential for zone-selective interlocking schemes. Making capacity (Icm) peaks at 220 kA at 415 V AC, which is the peak asymmetrical current the breaker can close into and latch. Maximum breaking time is 25 ms, fast enough to limit let-through energy for cable and busbar protection.

Fixed-mount design on rails or base plate. Connection pitch is 115 mm. Both upside and downside connections accept front or rear termination — rear connection is typical for switchboard busbar stabs; front connection suits cable-entry panels. Neutral position is right. Dimensions: 537 mm wide, 352 mm high, 300 mm deep. Panel cutout and busbar spacing must accommodate the fixed footprint — no slide-in cradle here.

Environmental and operational limits

Altitude derating: full rating up to 2000 m, derated above to 5000 m. IP30 enclosure means protection against tools >2.5 mm but not water — install in a clean, dry switchboard or enclosure. Power dissipation 420 W — factor into panel ventilation calculations.

Frequently asked questions

Where can I buy LV848181 and how do I get a price?

The LV848181 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is LV848181's rated breaking capacity at 415 V AC?

The LV848181 has an H2 performance class with 100 kA ultimate breaking capacity (Icu) at 415 V AC, and the service breaking capacity (Ics) also equals 100 kA at that voltage.

MPN