Skip to main content
Schneider Electric LV848181

LV848181 MasterPact MTZ2 3200A Circuit Breaker, 100 kA

MPN LV848181
Active

Schneider Electric MasterPacT MTZ2, LV848181, fixed circuit breaker, 4P, 3200 A at 40 °C, H2 100 kA 415 V AC, push-button control, IP30.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848181 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848181 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ2 3200 A — fixed-mount power breaker

The LV848181 is a Schneider Electric MasterPact MTZ2 fixed circuit breaker, 4-pole, rated 3200 A at 40 °C. Selectivity category B confirms it is designed for full discrimination downstream, critical for a main breaker in a distribution panel where you want only the faulted branch to trip.

Breaking performance and coordination

Rated short-time withstand current (Icw) is 85 kA for 0.5 s and 1 s, 75 kA for 3 s. That Icw figure governs the breaker's ability to hold a fault while downstream breakers clear — essential for zone-selective interlocking schemes. Making capacity (Icm) peaks at 220 kA at 415 V AC, which is the peak asymmetrical current the breaker can close into and latch. Maximum breaking time is 25 ms, fast enough to limit let-through energy for cable and busbar protection.

Fixed-mount design on rails or base plate. Connection pitch is 115 mm. Both upside and downside connections accept front or rear termination — rear connection is typical for switchboard busbar stabs; front connection suits cable-entry panels. Neutral position is right. Dimensions: 537 mm wide, 352 mm high, 300 mm deep. Panel cutout and busbar spacing must accommodate the fixed footprint — no slide-in cradle here.

Environmental and operational limits

Altitude derating: full rating up to 2000 m, derated above to 5000 m. IP30 enclosure means protection against tools >2.5 mm but not water — install in a clean, dry switchboard or enclosure. Power dissipation 420 W — factor into panel ventilation calculations.

MPN
LV848181