Schneider Electric LV848184 — Circuit Breaker Accessories

LV848184 MasterPact MTZ2 4P 1000A Fixed Circuit Breaker, H1

MPNLV848184
Active

Schneider Electric MasterPact MTZ2, LV848184, 4P 1000 A fixed circuit breaker, H1 66 kA 415 V AC, Category B, without control unit.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV848184 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ2
Product rangeMasterPacT
Device applicationPower distribution protection

Electrical

LV848184 — Electrical
ParameterValue
Rated current [In]1000 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P

Protection & Performance

LV848184 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 500/525 V AC 50/60 Hz 66 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability25000 cycles with periodic preventive maintenance
Electrical durability10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3

Mechanical

LV848184 — Mechanical
ParameterValue
Connection pitch115 mm
Downside connectionFront Rear
Upside connectionFront Rear
Device short nameMTZ2 10 H1
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width537 mm
Height352 mm
Depth300 mm

Environmental

LV848184 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C

Approvals

LV848184 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The LV848184 is a fixed-mounted MasterPact MTZ2 circuit breaker from Schneider Electric, 4-pole, rated 1000 A at 40 °C, with H1 performance level — 66 kA interrupting capacity at 415 V AC. It's a Category B breaker, meaning it's fully rated for selectivity in power distribution protection schemes where you need coordinated fault isolation downstream. This is a bare breaker — no control unit fitted. You'll add the trip unit separately. That's typical for a spec'd-in breaker where the protection settings are defined at the panel design stage, not a shelf-stocked unit.

Rated operational voltage is 690 V AC 50/60 Hz, with an insulation voltage of 1000 V AC — so it lives comfortably in 400 V and 480 V distribution panels and still has headroom for 690 V industrial supplies. The impulse withstand voltage of 12 kV tells you it handles transient overvoltages in an industrial environment without flashover. Service breaking capacity (Ics) is 66 kA across the board — 220/415 V, 440 V, 500/525 V, and 660/690 V AC. That's a uniform 100% rating, not a derated service value. Short-time withstand (Icw) is 66 kA for 0.5 s and 1 s, dropping to 36 kA at 3 s — essential data for selective coordination studies with downstream breakers. Mechanical durability is 25,000 cycles with periodic preventive maintenance; electrical durability is 10,000 cycles at 440 V and 690 V AC under EN/IEC 60947-2, and 6,000 cycles under AC-3 motor-switching duty per EN/IEC 60947-3. For a 1000 A frame, that's solid — this breaker is built for a main or large feeder position, not frequent switching. Power dissipation is 70 W at rated current. Factor it into your thermal calculation, especially if the panel is IP-rated and sealed.

Fixed mounting on rails or a base plate. Connection pitch is 115 mm. Both upside and downside connections accept front or rear terminations — gives you flexibility in busbar or cable routing. Neutral is on the right. Dimensions: 537 mm wide, 352 mm high, 300 mm deep. That's a substantial footprint — plan the panel layout accordingly. IP30 protection per EN 60529 — basic finger protection, not washdown. This lives inside a switchboard or enclosure, not in a wet environment.

Altitude rating: 0–2000 m no derating, 2000–5000 m with derating. That covers most installations except high-altitude mining or mountain-top sites above 5000 m.

Frequently asked questions

What is LV848184's rated breaking capacity?

The H1 performance grade delivers 66 kA service breaking capacity (Ics) at 220/415 V, 440 V, 500/525 V, and 660/690 V AC 50/60 Hz. Short-circuit making capacity (Icm) is 145 kA across those same voltages.

MPN