Skip to main content
Schneider Electric LV848194 — Circuit Breaker Accessories

Schneider MasterPact MTZ3 LV848194, 4000 A 4P H1 100 kA

MPNLV848194
Active

Schneider Electric MasterPacT MTZ3, LV848194, fixed 4-pole circuit breaker, 4000 A rated current, H1 100 kA breaking capacity at 415 V AC, Category B, rear connection.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LV848194 — Identification
ParameterValue
Product / component typeCircuit breaker
Product nameMasterPact MTZ3
Product rangeMasterPacT
Device applicationPower distribution protection

Electrical

LV848194 — Electrical
ParameterValue
Rated current [In]4000 A at 40 °C
Rated operational voltage [Ue]690 V AC 50/60 Hz
Rated insulation voltage [Ui]1000 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]12 kV
Poles description4P

Protection & Performance

LV848194 — Protection & Performance
ParameterValue
Rated service breaking capacity [Ics]100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 100 kA at 500/525 V AC 50/60 Hz 100 kA at 660/690 V AC 50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability10000 cycles with periodic preventive maintenance
Electrical durabilityAC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 1500 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 1500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 AC-23A: 1500 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 AC-23A: 1500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3

Mechanical

LV848194 — Mechanical
ParameterValue
Connection pitch230 mm
Downside connectionRear
Upside connectionRear
Device short nameMTZ3 40 H1
Control typePush-button
Mounting modeFixed
Mounting supportRails Base plate
Width997 mm
Height352 mm
Depth300 mm

Environmental

LV848194 — Environmental
ParameterValue
IP degree of protectionIP30 conforming to EN 60529
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C

Approvals

LV848194 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H IEC 61557-12

Product details

The LV848194 is a MasterPact MTZ3 fixed-mount circuit breaker rated 4000 A at 40 °C, 4 poles, with an H1 performance class delivering 100 kA Icu/Ics across the full voltage range up to 690 V AC. That 100 kA Ics at 440 V means it clears a fault and can be immediately reclosed without inspection — a key spec for selective coordination in industrial distribution where you need Category B selectivity (the breaker itself is rated Category B per IEC 60947-2). The Icw of 100 kA for 3 seconds tells you it withstands delayed clearing from downstream breakers, so it works as a main or tie breaker in a switchboard where fault-rating coordination is required. The 220 kA making capacity (Icm) covers the worst-case peak asymmetrical fault on a 415 V system. The 25 ms maximum breaking time and 80 ms closing response time are the numbers to plug into your arc-flash study.

Deployment context

The 260 W power dissipation at rated current matters for enclosure cooling calculations; factor that into the switchgear ventilation design.

The H1 performance class is Schneider's designation for 100 kA Icu at 415 V; the Ics equals Icu at all voltage levels up to 690 V, which is unusual and valuable for coordination studies.

Frequently asked questions

Where can I buy LV848194 and get a price?

The LV848194 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the closest alternative to LV848194 in the MasterPact family?

Within the same MTZ3 platform, the closest alternative would be a different performance class (H2 or) or a different frame size (MTZ3 32 for 3200 A). The H1 100 kA variant is the standard choice for 4000 A main breakers; stepping to H2 (150 kA) would be needed only if the fault current exceeds 100 kA at the point of installation.

What compliance documentation does Schneider provide for LV848194?

The breaker is certified to EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H. It carries CE marking for the European market. The IEC 61557-12 standard applies when the breaker is equipped with the power metering option. RoHS and REACH declarations are available from Schneider Electric's documentation portal.

MPN
LV848194